3 reviewing active alarms using the alarm menu – Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual

Page 64

Advertising
background image

Troubleshooting the Drive Using the OIM

7-5

Faults can also be reset without clearing the fault log by:

Pressing

when the drive is stopped and the control source is set to OIM.

Asserting fault reset from the selected control source.

To reset the faults and clear the fault log:

Step 1. Select Clear Fault Log and Reset Faults from the Fault Menu. Press

.

Step 2. The message “ATTENTION! DRIVE FAULTS HAVE BEEN RESET. FAULT

LOG HAS BEEN CLEARED” is displayed. The FAULT indicator is turned off,
the faults are reset, and the fault log is cleared.

Step 3. Press

to return to the Fault Menu.

Step 4. Press

again to return to program or monitor mode.

Important: You cannot clear individual faults. This procedure clears the entire fault

log.

7.3

Reviewing Active Alarms Using the Alarm Menu

You can review active alarms using the Alarm Menu. Alarms are not logged.

To review active alarms:

Step 1. Press

until ALARM is displayed in the key indicator. The screen

shown in figure 7.6 is displayed.

Figure 7.6 – Alarm Menu