2 selecting the control source – Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual

Page 58

Advertising
background image

6-4

GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0

6.2

Selecting the Control Source

Use

to select the control source for the drive.

The control source can be set to one of four options:

LOCAL: The drive’s front panel keypad/display is used to control the drive.

TERMBLK: The signals at the Regulator board terminal strip control the drive.

OPTION: An option board, such as the AutoMax Communication Network board, controls
the drive.

OIM: The OIM keys control the drive.

To select the control source:

Step 1. Stop the drive if it is running.

Step 2. Press

. The CONTROL SOURCE SELECT screen is displayed, as shown

in figure 6.4.

Step 3. Use

or

to move the cursor to the control source your want.

Step 4. Press

to accept the new control source and return to the previous

screen.

When the control source is changed to OPTION or TERMBLK,

is

automatically set to AUTO. When the control source is changed from OPTION or

TERMBLK to OIM or LOCAL,

is automatically set to MANUAL. When the

control source is changed from OIM to LOCAL or vice versa, the

setting is not

changed.

Figure 6.4 – CONTROL SOURCE SELECT Screen