6 oim failures – Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual
Page 67
 
7-8
GV3000/SE Operator Interface Module (OIM) User Guide, Version 2.0
7.6
OIM Failures
There are three OIM failure states: link failure, fatal OIM errors, and fatal regulator 
failures. If one of these failures occurs, a message is displayed if possible. Refer to 
table 7.2 for a list of OIM failure causes and corrective actions.
If the OIM is not the control source, an OIM failure does not affect drive operation. If 
the OIM is the control source, an OIM failure causes the drive to stop.
!
ATTENTION:
is not active if an OIM failure occurs. Use another
control source to stop the drive. Failure to observe this precaution could 
result in severe bodily injury or loss of life.
Table 7.2 – OIM Failure Causes and Corrective Actions
Failure State
Cause
Corrective Action
Link Failure
Communication between the OIM 
and Regulator board is lost. This 
can occur if the cable between 
them is disconnected.
Check the cable between the OIM and the 
Regulator board.
The OIM attemps to re-establish 
communication. If it succeeds, the message 
“Press CANCEL to continue” is displayed. 
Press
to return to program or
monitor mode.
Fatal OIM Error (FATAL 
KEYPAD ERROR is 
displayed on OIM)
•
FAULT CODE = 14
A version 1.x OIM is connected to a 
version 6.x or later GV3000/SE 
drive.
Replace the version 1.x OIM with a version 
2.x or later OIM.
•
FAULT CODE = 22
A FlexPak 3000 OIM is connected 
to the GV3000/SE drive.
Replace the FlexPak 3000 OIM with a 
GV3000/SE OIM.
•
All Other Fatal OIM 
Errors
The OIM did not pass 
self-diagnostics.
Cycle drive power. If this does not correct 
the problem, contact Reliance Electric for 
assistance. 
Fatal Regulator Failure
There is a problem with the drive.
Cycle drive power. If this does not correct 
the problem, contact Reliance Electric for 
assistance.