5 clearing a programming error screen – Rockwell Automation GV3000/SE Operator Interface Module (OIM) User Guide User Manual
Page 66
 
Troubleshooting the Drive Using the OIM
7-7
Step 2. If the DRIVE READY indicator is off, the drive is not ready to start. If this is
the case, move the cursor to “Why is the drive not ready?” and press
.
The screen shows possible explanations of why the drive is not ready. If the
▼
symbol is displayed, more information is available. Press
to read the
rest of the screen. Table 7.1 lists all possible responses.
Step 3. Press
to exit the screen.
Step 4. Press
again at the Diagnostics Menu to return to program or monitor
mode.
7.5
Clearing a Programming Error Screen
Programming errors occur if you select an option that is not valid, such as attempting 
to set a read-only parameter. These errors do not affect drive operation and are not 
logged. To remove the programming error message, press
.
Table 7.1 – Possible OIM Responses to “Why is the Drive Not Ready?”
Display
Description
PRE-CHARGE IS NOT READY
The DC bus is not within required tolerance.
FP STOP ACTIVE
The front-panel STOP key is asserted.
SERIAL STOP ACTIVE
The serial port (CS3000) stop input is 
asserted.
ACTIVE CS STOP ACTIVE
The active control source stop input is 
asserted.
DRIVE NOT IDENTIFIED
The Power Module has not been identified to 
the regulator.
DOWNLOAD IN PROGRESS
The CS3000 configuration download 
procedure is in progress.
COAST/DB STOP OPEN
The coast/DB stop input (TS 23) is open.
CUSTOMER INTERLOCK OPEN
The function loss input (TS 20) is open.
MEMORY OPERATION IN 
PROGRESS
Non-volatile memory is being restored.
DRIVE IS IN PROCESS OF 
STOPPING
The drive is in the process of stopping.
THERE IS A DRIVE FAULT(S)
The drive is faulted.
THE DRIVE IS READY.
The drive is ready to run.
A STOP INPUT IS ACTIVE
A keypad stop key or the selected control 
source stop input is asserted.