If the motor nameplate shows the no-load current, this parameter value can be 
calculated using the following formula. If no-load current is not on the motor 
nameplate, perform the self-tuning procedure to automatically calculate the result.
Note that this parameter is only displayed if REGULATION TYPE (P.048) is set to 
VECTOR and if self-tuning was not performed.
The value of this parameter is automatically set if torque-control self-tuning is 
performed successfully.
MAGNET CURRENT PRCNT (U.006)
Identifies the 
percentage of 
magnetizing current 
(no-load amps) with 
respect to motor 
rated amps.
Parameter Range:
10.0 to 80.0%
Default Setting:
Power Module-dependent. See the software I/M for 
more information.
Parameter Type:
Configurable
!
ATTENTION: If this parameter is set incorrectly, overcurrent or 
excessive heating of the motor could result. Failure to observe this 
precaution could result in damage to, or destruction of, the equipment.
Magnetizing Current =
Motor Rated Amps
No-Load Amps
x 100