KEYENCE DL-EP1 User Manual

Page 108

Advertising
background image

5-5 Objects Usable by DL-EP1

5-20

Identity Object

5

App

end
ix

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT2) -

Reference 1) Details of status (16 bits)

Bit

Name

Description

0

Owned

ON: This bit is set to ON when one or more class1 or class3

connections are established.

1

Reserved

Always OFF.

2

Reserved

Always ON.

3

Reserved

Always OFF.

4 to 7

Extended Device

Status

Bits 4 to 7 are set according to the DL-EP1 status as follows:

0101(1): The DL-EP1 is in the unrecoverable fault status (1).

0010(2): The DL-EP1 is not (1) and one or more connections

have timed out.

0011(3): The DL-EP1 is neither (1) or (2) and no connection

is established.

0110(4): The DL-EP1 is not (1), (2), or (3) and there is one or

more connections that are in the RUN status.

0111:

The DL-EP1 is in a status other than (1) to (4).

8

Minor Recoverable

Fault

Always OFF.

9

Minor

Unrecoverable Fault Always OFF.

10

Major Recoverable

Fault

ON: This bit is set to ON when a recoverable unit error occurs.

The red MS LED flashes.

11

Major

Unrecoverable Fault

ON: This bit is set to ON when an unrecoverable unit error

(EEPROM read error, etc.) occurs.

The red MS LED is lit.

12 to 15

Reserved

Always OFF.