5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC

5-7

5

App

end
ix

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT2) -

2

Add "ETHERNET-MODULE (Generic Ethernet Module)".

3

Change the settings as required.

Name
Choose a name. The following tags are generated based on the name set
here, and are used as the data exchanged with cyclic communication.
• (Name): I

Data received from DL-EP1

• (Name): O Data sent to DL-EP1
• (Name): C

Not used.

Comm Format
Designate [Data INT].
IP Address
Designate the DL-EP1's IP address.
Input (DL-EP1 send data size)
• Instance number: 100 (decimal)
• Data size: Value up to 84
Output (DL-EP1 receive data size)
• Instance number 101 (decimal)
• Data size: Value up to 5
Configuration
• Instance number: 1 (decimal)
• Data size: 0