5-4 Procedures for Communicating with an Allen-Bradley ControlLogix PLC
5-10
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT2) -
5
App
end
ix
2
Add the MSG instruction to the RsLogix5000 ladder.
3
Open the "Configuration" tab in the Message instruction setting dialog,
and change the MSG instruction setting.
Message Type
Select "CIP Generic".
ServiceType, Class, Instance, Attribute
Designate a value which matches the message to be sent.
• Example 1: Writing data to DL Object "Bank 0 HIGH setting" when writing
data to attributes
Item
Setting Value
ServiceType
SetAttributeSingle
ServiceCode
- (Cannot be designated)
Class
67H
Instance
01H
Attribute
0341H
SourceElement
Name of tag storing send data
SourceLength
4 byte (attribute size is 4)
Destination
- (Cannot be designated)