Vsr-st, Vane type waterflow alarm switch with retard, For small pipe – Potter Releasing Systems User Manual

Page 100: Fig. 2, Fig. 1, Fig. 3 cover tamper switch, Fig. 5 typical electrical connections

Advertising
background image

100

FOR SMALL PIPE

PRINTED IN USA

MFG. #5401204- REV F

12/08

PAGE 2 OF 3

VSR-ST

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

DWG# 1146-3A

DWG# 8810018-2

C

(WHT)

N.O.

(RED)

N.C.

(BLK)

An uninsulated section of a single conductor should not be looped around the terminal and serve as
two separate connections. The wire must be severed, thereby providing supervision of the connection
in the event that the wire becomes dislodged from under the terminal.

Fig. 2

There are 12 paddles furnished with

each unit. One for each size of threaded,

sweat or plastic TEE as described in Fig.

1. The paddles have raised lettering that

show the pipe size and type of TEE that

they are to be used with. The proper

paddle must be used. The paddle must

be properly attached (see Fig. 3) and

the screw that holds the paddle must be

securely tightened.

Notes:
1. The model VSR-ST has two switches, one can be used to operate a

central station, proprietary or remote signaling unit, while the other

is used to operate a local audible or visual annunciator.

2. For supervised circuits see “Switch Terminal Connections”

drawing and CAUTION note (Fig. 4).

Fig. 4 Switch Terminal Connections Clamping Plate Terminal

OUTGOING

INCOM

ING

DWG# 923-3

Approximate Depth Requirement

Tee Size

Threaded

Sweat

CPVC

1" X 1" X 1"

2-1/16"

1-3/4"

2-7/16"

1-1/4" X 1-1/4" X 1" 2-7/16"

2-7/16"

N/a

1-1/2" X 1-1/2" X 1" 2-11/16"

2-1/4"

N/a

2" X 2" X1"

3-3/16"

2-3/4"

N/a

Fig. 1

Screw the fitting into the TEE fitting as shown.

On sweat TEE's, no threaded bushings, inserts or adapters are

permitted unless they comply with the dimensions listed in the

chart below.
Important - the depth to the inside bottom of the TEE should

have the following dimensions:

Fig. 3

Cover Tamper Switch

(Shown with cover in place)

Shown with optional Cover Tamper Switch.

Retard Adjustment:

The delay can be adjusted by rotating

the retard adjustment knob from 0

to the max setting (60-90 seconds).

The time delay should be set at the

minimum required to prevent false

alarms.

Do not leave cover off for an

extended period of time.

Fig. 5 Typical Electrical Connections

DWG# 1204-1A

RETARD

ADJUSTMENT

KNOB

MOUNT SO ARROW

ON BASE POINTS

IN DIRECTION OF

WATERFLOW

1" NPT MALE FITTING

ON ALL SIZES

RUN OF THE TEE

MAY BE 1" , 1 1/4", 1

1/2", OR 2"

INSURE THAT O-RING

IS IN O-RING GROOVE

BEFORE INSTALLING

SWITCH.

To prevent leakage apply teflon tape sealant to the

1" NPT male fitting only. Do not use any other type

of lubricant or sealant.

POSITIVE DC

OR HOT AC

NEGATIVE DC OR

NEUTRAL AC

WATERFLOW ZONE

ON FIRE PANEL

BELL

EOLR

NO NC COM

COM NC NO

Waterflow switches that are monitoring wet pipe sprinkler systems shall not

be used as the sole initiating device to discharge AFFF, deluge, or chemical

suppression systems. Waterflow switches used for this application may result in

unintended discharges caused by surges, trapped air, or short retard times.