12/09

PFC-4410RC

RELEASING CONTROL PANEL

Architects/Engineers Specifications

The control panel for the extinguishing agent releasing system shall be a

microprocessor based control capable of protecting multiple hazards in one

control panel. It shall be Underwriters Laboratories Inc. listed under Standard

864 Ninth Edition and Underwriters Laboratories of Canada for Local Control

Units for Releasing Service. The control shall also be approved by Factory

Mutual Research Corporation and be compliant with the requirements of

NFPA-72 (Local: A, M, SS service types; DAC and NC signaling type) and

NFPA12, NFPA12A, NFPA-13, NFPA-15, NFPA-16, NFPA-17, NFPA-17A,

NFPA-750, and NFPA-2001.
The control shall be housed in an 18 gauge steel cabinet that has a hinged,

removable door with a key lock. The finish shall be baked enamel and

available in red or off-white with contrasting trim and logo. An optional

matching bezel should be available for semi-flush mounting. The cabinet shall

have adequate space to house 18 AH standby batteries capable of operating

the system for at least 90 hours.
The control shall include a fully supervised integral power

supply/battery charger capable of providing 200mA to the auxiliary power

circuit. It shall also be capable of providing 2.5 Amps to all releasing and

notification appliance circuits combined. All initiating, output and auxiliary

power circuits shall be power limited.
The control shall have a 32 character (16 characters, 2 lines) backlit LCD

display and a 34 LED supplemental display. All diagnostic and alarm

event information shall be viewable in text form on this display. A field

programmable custom banner message with the current date and time shall

be displayed when no current alarm or diagnostic information exists.
All operational features of the control panel shall be field programmable using

menu driven selections on the alpha-numeric display and on board controls.

No special programmer will be required and jumpers or switches to configure

operational features shall not be permitted. Alarm and trouble indications

shall resound when required.
The control panel shall be equipped with 19 programs built into the panel

memory, 13 for water based extinguishing and 6 for agent extinguishing.

In addition, the panel shall have the ability to add custom programs. All

programming functions shall be password protected.
The control shall have four fully supervised Class B (Style B) initiating circuits

capable of supporting the operation of 25 compatible 2-wire smoke detectors

on each circuit.
The individual circuits shall be selectable through the programming sequence

to operate in one of the following modes: Conventional, Waterflow, Linear

Heat Detection (up to 10,000 feet per zone), Manual Release, Low Air Alarm,

Supervisory, Tamper, Low Air or High Air.

Optional Class A modules, CA2Z, may be added for Class A operation. The

panel shall have a Low Air Zone that creates a supervisory condition and map

to an output. UL and ULC Listed, FM Approved, NYMEA Accepted, CSFM

Approved
The control shall have two fully supervised Class B (Style B) supervisory

circuits. These circuits shall be selectable through the programming

sequence to operate in one of the following modes: Supervisory, Tamper, Low

Air or High Air.
The control shall have one fully supervised class B (style B) Abort circuit with

3 different operating modes, ULI, IRI, and NYC.
The control shall have four fully supervised Class B (Style Y) output circuits.

These circuits shall be selectable through the programming sequence to

operate as one of the following: Alarm Notification Appliance, Supervisory

Notification Appliance, Trouble Notification

Appliance or Releasing. The optional CAM module may be added to convert

the outputs to Class A.
The panel shall have an RS-485 output and auxiliary power outputs for

connection and supervision of up to 4 remote annunciators or an ARM-44

Relay Module and 3 annunciators.
The releasing circuits shall be supervised for short circuit conditions and shall

be programmable for cross zoning operation when required. The discharge

timer for these releasing circuits shall be programmable for times of 7, 8, 9,

10, 20 minutes or continuous. All initiating and

output circuits shall be capable of being individually disabled or enabled. In

addition, when in the agent extinguishing mode there shall be a pre-discharge

timer adjustable from 0-60 seconds from an alarm zone or 0-30 seconds from

a manual release zone.
The control shall have a test mode that will automatically disable all releasing

circuits. The test mode shall operate in such a manner as to automatically

reset the initiating circuit and indicating circuits after detecting each alarm

condition initiated by the test. All testing shall be recorded in the 40 event

history buffer. The test mode will automatically terminate after twenty minutes

of inactivity.
The control shall have four integral relay contacts rated 3 Amps at 30 VDC for

connection to external auxiliary equipment. One relay shall operate when an

alarm condition occurs, another when a trouble signal occurs, the third when a

supervisory condition occurs, and the fourth during a waterflow condition.
UL and ULC Listed, FM Approved, NYMEA Accepted, CSFM Approved.