AIR PRESSURE SUPERVISION

Dry Pipe System Waterflow And Air Supervisory Switch

Selection Guide

Fig. 9

PS40 SHOULD BE

INSTALLED IN LINE

WITH “BVL” VALVE

FOR TEST PURPOSES

PS40-1

LOW PRESSURE (SET AT 30 PSI)

PS40-2

LOW AND HIGH PRESSURE

(SET AT 30 AND 50 PSI)

Note: Unless excess pressure is pumped into the system, the waterflow device should have a retard. Per NFPA

72 2010 23.8.5.10.4, there shall be no shut-off valve in line to a pressure type waterflow switch, unless the shut-

off is electrically supervised. Potter Model RBVS can electrically supervise shut-off ball valves.

WATERFLOW

SWITCH

PS10-1

SINGLE CONTACT

PS10-2

DOUBLE CONTACTS

TO WATER

MOTOR GONG

PS10

PETCOCK

(OPEN)

WATER BY-PASS

TEST VALVE

(CLOSED)

CHECK RBVS

BALL DRIP

VALVE

ALARM LINE

SHUT-OFF VALVE,

SUPERVISED

(OPEN)

DRIP

CUP

WATER

PRESSURE

GAUGE

CHECK

WATER PRESSURE

FROM CITY MAINS

DRAIN

PIPE

DWG# 8704200-7A

OS & Y

CONTROL VALVE

(OPEN)

TAMPER

DEVICE

OSYSU

DRAIN VALVE (CLOSED)

INTERMEDIATE

CHAMBER

SHUT-OFF VALVE

(CLOSED)

WATER LEVEL

AIR

PRESSURE

PRIMING

CHAMBER

BVL BLEEDER

TEST VALVE

(OPEN)

AIR PRESSURE

GAUGE

PS40

RISER TO

SPRINKLER HEADS

TO AIR SUPPLY

AIR

SUPPLY

VALVE

(OPEN)

CHECK