Potter Releasing Systems User Manual

Page 18

Advertising
background image

18

#2. Wet System With An Alarm Check Valve:
This type of system has an alarm check valve, the valve is basically a check valve with an alarm port. The main

purpose of the alarm check valve is to ring a mechanical bell called a water motor gong. The valve should, (if

properly maintained), help hold the system pressure steady and reduce the possibility of false alarms. Under

normal circumstances, the clapper of the valve is closed, blocking the alarm port, maintaining the system

pressure, and preventing the sprinkler system water from leaking back into the city supply. When a sprinkler

opens due to fire, or there is a large surge in the city pressure, the clapper of the valve opens. The alarm port is

now exposed to the incoming water supply. When the pressure at the switch reaches 6 psi, the pressure switch

trips, or the retard time starts on the pressure switch with built in retard. This alarm port may be piped to the

outside of the building through a water motor gong.

These systems can use a vane type flow switch with a retard or they can use a pressure type flow switch. The

pressure type flow switch would be installed on the alarm port, in line with a water motor gong if one is being

used. The pressure switch must either be installed on top of a retard chamber, (see Fig. 3), or a pressure switch

with a built in retard, (see Fig. 4), must be used to prevent false alarms due to water surges. There must be an

automatic drain on this line to allow the water to drain and the pressure to drop back to zero so the pressure

switch can reset after a surge or activation of the alarm valve.

Pressure type flow switches can be installed without disabling the sprinkler system. Since they are installed on

the alarm port, there is no pressure or water present under normal circumstances. The sprinkler system does not

have to be drained, they can be installed without shutting off the water supply. Therefore the sprinkler system is

never out of service.

Retard chambers are metal containers that fill with water when there is a surge in city pressure. They absorb

the pressure increase thereby allowing the pressure switch to only operate in an actual alarm condition. There

is an automatic drain at the bottom of the chamber to allow the surge to drain out. Retard chambers require

maintenance to make sure that the drain stays clear and doesn’t get clogged with rust or corrosion. If a surge

does not drain from the retard chamber before another surge happens, the retard chamber may fill causing the

pressure switch to send a false alarm.

A pressure switch with a built in retard allows the system to remain operational at all times, and eliminates the

maintenance required on the retard chamber. An automatic drain is still required to relieve the pressure on the line.

Note: All water control valves shall be supervised per NFPA13 2010 8.16.1.1.2.1. Pressure type flow switches

must be installed before any shut-off valve, or such valve must be electronically supervised.

Advertising
This manual is related to the following products: