Potter Releasing Systems User Manual

Page 62

Advertising
background image

62

Table 2

Secondary Power Supply Requirements

Service

Use

Standby

Time

Alarm

Time

NFPA 72

• Central Station (PPU)

24 hrs.

5 mins.

• Local

24 hrs.

5 mins.

FMRC 1011 and 1012, Deluge and Pre-action Systems

90 hrs.

10 mins.

Where requested by FM or others.

90 Hours is not a UL requirement.

Calculation Table

1 2 3

4

5

6

Module/Device Quantity Standby mA Per Unit Total Standby Current Alarm mA Per Unit Total Alarm Current

Table 1

Current Requirements

*Add 23 mA plus current requirement of all devices connected for each output programmed as Trouble Bell

**Includes one zone short circuit current.

x 0.001

x 0.001

Total mA

Convert to A

Total A

5 min/12 or 10 min/6

Total Alarm AH

+ Total Standby AH

Total AH

Efficiency Factor

Required AH

Total mA

Convert to A

Total A

Multiply by hours from table 2

Total Standby AH

÷ ___

Use a battery with a higher AH rating than Required AH

÷ 0.85

x ___

Module/Device

Standby mA*

Alarm mA*

PFC-4410RC

121

274

RA-4410RC

12

12

Advertising
This manual is related to the following products: