Water column switch – Potter Releasing Systems User Manual

Page 104

Advertising
background image

104

GROUND SCREW

YELLOW "WATER" LED

GREEN "POWER" LED

PROBE

TERMINAL BLOCK

DWG. #1158-3

PAGE 3 OF 3

PRINTED IN USA

Control Unit Mounted On Probe

Probe Spacing Requirements (Fig. 1)

Note: Mount only with probe facing horizontally or vertically

downward. Do not mount with probe angled upward. Maintain probe

clearances as indicated.

Installation (Fig. 3)

Probe Cleaning And Replacement (Fig. 4)

Probe must be inspected annually for scale build-up. Clean all scale from

probe and teflon sleeve taking care not to damage the teflon sleeve.
Probe should be replaced every 10 years.
The Control Unit should be replaced every 15 years. In areas of

high humidity and heavy dust or other airborne contaminants, more

frequent replacement may be required.

DWG. #1158-1

1/4" MIN.

1/4" MIN.

1/4"

MIN.

TEFLON SLEEVE INSULATOR

(Be careful not to damage during cleaning)

DWG #1108-8

DWG. #1158-2

MOUNTING SCREWS

PROBE LOCK WASHER

AND NUT

MOUNTING

SCREW

MOUNTING

SCREW

MFG. #5401158 - REV D

5/08

WCS

WATER COLUMN SWITCH

Probe Installation (Fig. 2)