Pre-action (single-interlock) systems – Potter Releasing Systems User Manual

Page 54

Advertising
background image

54

section of piping. When water flows into the system, it also flows into this port. The flow switch will operate

when the pressure reaches 6 psi. These devices do not need a retard as there should be no water surges. This

device does not need adjusting.
The waterflow switch will not trip until after the release panel goes into alarm and operates the release circuit

which opens the valve and allows water to flow into the system.

Low Air Pressure Switch: PS40-1, PS40-2, PS10-1, PS10-2

The pressure on single and double interlock systems must be monitored to ensure the integrity of the piping.

On double interlock systems, a low air switch with two switches can be used. One switch could be set to trip

first for a low air SUPERVISORY condition which would indicate a loss of air pressure possibly due to a failed

compressor. The other switch could be set to trip a few psi lower for the low air ALARM. Then when a smoke

or heat detector and the low air ALARM switch are both in alarm at the same time, the release panel will trip

the solenoid. On systems with 5-15 psi, the PS10-1 will provide a low signal at 4 psi. It can be adjusted to trip

between 4-15 psi. For systems with more than 15 psi, the PS40-2 will provide a low signal at 30 psi. It can be

adjusted to trip between 10-60psi. To change the pressure settings, remove pressure from the device. Adjust the

thumb wheel until the top of the wheel corresponds with the desired pressure setting on the scale. The switch

should trip at approximately that pressure on a drop. Pressure supervisory switches should have a bleeder valve,

model BVL installed in line for testing purposes.

Pre-Action (Single-Interlock) Systems

Pre-Action systems are basically dry pipe systems, except they use an electrically operated valve to hold

back the water supply instead of a dry pipe valve. They are designed to overcome the operational delay of

conventional dry pipe systems, and to eliminate the possibility of accidental water damage caused by accidental

damage to the sprinkler heads or system piping.
The water supply valve is operated independently of the opening of sprinklers. The valve is opened by the

operation of a releasing panel which is monitoring initiating devices such as smoke or heat detectors, not by the

fusing of sprinklers.
Single interlock systems use closed sprinklers attached to a piping system containing supervisory air pressure.

The water is held back by an electrically operated valve. The valve is connected to a compatible releasing panel.

The panel is monitoring initiating devices such as smoke or heat detectors, and manual stations, that are located

in the same area as the sprinkler heads. These devices are connected to the releasing panels alarm initiating

zones. A low air pressure supervisory switch is used to monitor the supervisory pressure in the piping system, it

is connected to a supervisory zone on the release panel.
If the system pressure drops due to an open sprinkler, damaged pipe, or air compressor failure, the pressure

switch will cause a supervisory condition on the release panel, the valve will not open. If the smoke or heat

detectors operate or if a manual station is activated, the release panel will go into an alarm condition, causing

the release circuit on the panel to energize which will allow the valve to open and water to flow into the system

piping, even if no sprinklers have opened.

Typical System Configuration (PFC-4410RC Program #1)
Initiating [ inputs ]

Zone #1 - Conventional Alarm Zone - Smoke or Heat detectors

Zone #2 - Conventional Alarm Zone - Smoke or Heat detectors

Zone #3 - Waterflow Zone - Pressure type waterflow switch

Zone #4 - Manual Station Zone - Pull Stations

Sup #1 - Supervisory Zone - Valve tamper and/or low air supervision

Sup #2 - Supervisory Zone - Valve tamper and/or low air supervision

Indicating (outputs)

#1 - General Alarm - Operates as soon as the panel detects an alarm condition.

#2 - Waterflow Bell - Operates when the waterflow switch detects water flowing into the system.

#3 - Release - Opens the Solenoid to allow water into the system after the panel goes into alarm.

#4 - Supervisory - Bell or horn to indicate a supervisory condition.