When installing the smaller flow switches that screw into a tee fitting, the proper size tee must be used. Never

use a reducing bushing to make the switch fit the tee. Bushings prevent the paddle from being in the proper

location in the tee. Also make certain that the correct paddle for the size and type of piping is being used and

that the paddle is on the stem tight. The flow switch must be screwed into the tee the proper depth.
After the installation is complete, slowly open the water control valve and open the inspector’s test valve

located at the far end of the system. This will help prevent air from being trapped in the system.

Screw the device into the TEE fitting as shown. Care

must be taken to properly orient the device for the

direction of the waterflow.

Fig. 12

Fig. 13

COVER TAMPER SWITCH

MOUNT SO

ARROW ON

BUSHING POINTS

IN DIRECTION OF

WATERFLOW

1” NPT

THREADED

FITTING ON

ALL SIZES

RUN OF THE TEE

MAY BE

THREADED OR

SWEAT PIPE

DIRECTION OF

WATERFLOW

DWG# 802-30A