Ps10 series, Pressure switch – Potter Releasing Systems User Manual

Page 77

Advertising
background image

77

MFG. #5400928 - REV D

1/08

PRINTED IN USA

PAGE 1 OF 3

PS10 SERIES

PRESSURE SWITCH

Patent Pending

Installation

The Potter PS10 Series Pressure Actuated Switches are designed for the

detection of a waterflow condition in automatic fire sprinkler systems of

particular designs such as wet pipe systems with alarm check valves, dry

pipe, preaction, or deluge valves. The PS10 is also suitable to provide a

low pressure supervisory signal; adjustable between 4 and 15 psi (0,27 and

1,03 BAR).

1. Apply Teflon tape to the threaded male connection on the device.

(Do not use pipe dope)

2. Device should be mounted in the upright position (threaded connection down).

3. Tighten the device using a wrench on the flats on the device.
Wiring

Instructions

1. Remove the tamper resistant screw with the special key provided.

2. Carefully place a screwdriver on the edge of the knockout and

sharply apply a force sufficient to dislodge the knockout plug. See Fig 9

3. Run wires through an approved conduit connector and affix the connector

to the device.

4. Connect the wires to the appropriate terminal connections for the

service intended. See Figures 2,4,5, and 6. See Fig 7 for two switch, one

conduit wiring.
Testing

The operation of the pressure alarm switch should be tested upon completion

of installation and periodically thereafter in accordance with the applicable

NFPA codes and standards and/or the authority having jurisdiction

(manufacturer recommends quarterly or more frequently).
Wet System

Method 1: When using PS10 and control unit with retard - connect PS10

(UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA

Accepted, CE Marked Pending)
Dimensions:
3.78" (9,6cm)W x 3.20" (8,1cm)D x 4.22" (10,7cm)H
Conduit Entrance: Two knockouts provided for 1/2" conduit. Individual

switch compartments and ground screws suitable for

dissimilar

voltages.

Enclosure: Cover - Die-cast with textured red powdercoat finish, single

cover screw and rain lip.
Base - Die-cast
Pressure Connection: Nylon 1/2" NPT Male
Factory Adjustment: 4 - 8 PSI (0,27 - 0,55 BAR)

Differential: 2 PSI (0,13 BAR) typical
Maximum System Pressure: 300 PSI (20,68 BAR)
Switch Contacts: SPDT (Form C)

10.1 Amps at 125/250VAC, 2.0 Amps at 30VDC

One SPDT in PS10-1, Two SPDT in PS10-2
Environmental Specifications:

NEMA 4/IP55 Rated Enclosure - indoor or outdoor when used

with NEMA 4 conduit fittings.

Temperature range: -40°F to 140°F (-40°C to 60°C)

Service Use:

Automatic Sprinkler

NFPA-13

One or two family dwelling

NFPA-13D

Residential Occupancy up to four stories

NFPA-13R

National Fire Alarm Code

NFPA-72

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833

• www.pottersignal.com

into alarm port piping on the input side of retard chamber and electrically

connect PS10 to control unit that provides a retard to compensate for surges.

Insure that no unsupervised shut-off valves are present between the alarm

check valve and PS10.

Method 2: When using the PS10 for local bell application or with a control

that does not provide a retard feature - the PS10 must be installed on the alarm

outlet side of the retard chamber of the sprinkler system.

Testing: Accomplished by opening the inspector's end-of-line test valve.

Allow time to compensate for system or control retard.

Note: Method 2 is not applicable for remote station service use, if there is an

unsupervised shut-off valve between the alarm check valve and the PS10.
Wet System With Excess Pressure

Connect PS10 into alarm port piping extending from alarm check valve.

Retard provisions are not required. Insure that no unsupervised shut-off

valves are present between the alarm check valve and the PS10.

Testing: Accomplished by opening the water by-pass test valve or the

inspector's end-of-line test valve. When using end-of-line test, allow time

for excess pressure to bleed off.
Dry System

Connect PS10 into alarm port piping that extends from the intermediate

chamber of the alarm check valve. Install on the outlet side of the in-line

check valve of the alarm port piping. Insure that no unsupervised shut-off

valves are present between the alarm check valve and the PS10.

Testing: Accomplished by opening the water by-pass test valve.

Note: The above tests may also activate any other circuit closer or water

motor gongs that are present on the system.

Tamper

Cover incorporates tamper resistant fastener that requires a special key for

removal. One key is supplied with each device. For optional cover tamper

switch kit, order Stock No. 0090200. See bulletin #5401200 PSCTSK.

Ordering

Information

Model

Description

Stock No.

PS10-1

Pressure switch with one set 1340103

SPDT contacts

PS10-2

Pressure switch with two sets 1340104

SPDT contacts

Hex Key 5250062

Cover Tamper Switch Kit 0090200

Advertising
This manual is related to the following products: