VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

MFG. #5401146 - REV L

3/09

General Information

The Model VSR is a vane type waterflow switch for use on wet sprinkler

systems. It is UL Listed and FM Approved for use on steel pipe;

schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC

approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering

Information chart.

The VSR may also be used as a sectional waterflow detector on large

systems. The VSR contains two single pole, double throw, snap action

switches and an adjustable, instantly recycling pneumatic retard. The

switches are actuated when a flow of 10 GPM (38 LPM) or more occurs

downstream of the device. The flow condition must exist for a period

of time necessary to overcome the selected retard period.

UL, CUL and CSFM Listed, FM Approved, LPCB Approved, For

CE Marked (EN12259-5) / VdS Approved model use VSR-EU

Service Pressure: 450 PSI (31 BAR) - UL

Flow Sensitivity Range for Signal:

4-10 GPM (15-38 LPM) - UL

Maximum Surge: 18 FPS (5.5 m/s)

Contact Ratings: Two sets of SPDT (Form C)

10.0 Amps at 125/250VAC

2.0 Amps at 30VDC Resistive

10 mAmps min. at 24VDC

Conduit Entrances: Two knockouts provided for 1/2" conduit.

Individual switch compartments suitable

for dissimilar voltages.

Environmental Specifications:

• NEMA 4/IP54 Rated Enclosure suitable for indoor or

outdoor use with factory installed gasket and die-cast housing

when used with appropriate conduit fitting.

• Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL

• Non-corrosive sleeve factory installed in saddle.

Service Use:

Automatic

Sprinkler NFPA-13

One or two family dwelling

NFPA-13D

Residential occupancy up to four stories

NFPA-13R

National Fire Alarm Code

NFPA-72

Installation must be performed by qualified personnel and in

accordance with all national and local codes and ordinances.

• Shock hazard. Disconnect power source before servicing. Serious

injury or death could result.

• Risk of explosion. Not for use in hazardous locations. Serious

injury or death could result.

Ordering Information

Nominal Pipe Size

Model

Part Number

2"

DN50

VSR-2

1144402

2 1/2"

DN65

VSR-2 1/2

1144425

3"

DN80

VSR-3

1144403

3 1/2"

-

VSR-3 1/2

1144435

4"

DN100

VSR-4

1144404

5"

-

VSR-5

1144405

6"

DN150

VSR-6

1144406

8"

DN200

VSR-8

1144408

Specifications subject to change without notice.

Optional: Cover Tamper Switch Kit, stock no. 0090148

Replaceable Components: Retard/Switch Assembly, stock no. 1029030

Enclosure

The VSR switches and retard device are enclosed in a general purpose,

die-cast housing. The cover is held in place with two tamper resistant

screws which require a special key for removal. A field installable

cover tamper switch is available as an option which may be used

to indicate unauthorized removal of the cover. See bulletin number

5401103 for installation instructions of this switch.

Waterflow switches that are monitoring wet pipe sprinkler systems shall

not be used as the sole initiating device to discharge AFFF, deluge,

or chemical suppression systems. Waterflow switches used for this

application may result in unintended discharges caused by surges,

trapped air, or short retard times.