Potter Releasing Systems User Manual

Page 41

Advertising
background image

41

Visual Inspections Inspections are required at various frequencies as noted below. Use the Inspection

Forms at the end of this chapter to record all inspection results.

Daily

Dry Pipe Systems:

During freezing weather, the heated enclosure for the dry pipe valve

should be checked to assure it is adequately heated.

Weekly

All Sprinkler Systems:

Inspect control valves (if sealed).

Water supply valves, including post indicator and roadway valves,

should be checked to assure that they are open.

Inspect condition of sprinkler heads.

Heads should be checked to make sure they are not damaged or

blocked by storage and have not been painted or otherwise impaired.

Note: An 18 inch (457-mm) clear space must be maintained below the

sprinklers to assure an adequate discharge pattern. Attachment of 18-inch-

long paper or plastic streamers to the sprinkler piping helps remind people

working in storage areas of the minimum clear space requirement.

Dry Pipe Sprinkler Systems:

Inspect air pressure and water pressure gauges. Be sure that air

and water pressures are within the normal range for that

particular system.

Record pressure readings. It is recommended that the normal

pressure be noted on the gauge or a tag attached to it. A loss of

pressure of more than 10 percent should be investigated.

Monthly

All Sprinkler Systems:

Inspect fire department connections. Connections should be accessible and

visible at all times. Caps or plugs should be in place and threads clean,

undamaged and lightly lubricated with graphite.

The connection should be drained through the ball drip from the check valve

to assure it will not freeze.

Inspect control valves (if locked).

Water supply valves, including post indicator and roadway valves, should be

checked to assure that they are open.

Quarterly

Determine dry pipe system priming water level by slowly opening the

priming water level test valve. If only air escapes, close the test valve

and add priming water. This is done by closing the lower priming

valve, opening the upper priming valve, and adding approximately 1

quart of water through the priming funnel. The upper priming valve is

then closed and the lower priming valve opened, which allows the

water to run into the dry pipe valve. Again, check the test valve. If

water does not run out, repeat the procedure. When sufficient water

has been added so that water drains from the test valve, allow it to

drain until air begins to escape, then close the valve securely. Also be

(

sure the upper and lower priming valves are closed securely.

Advertising
This manual is related to the following products: