PAGE 1 OF 3

PS120 SERIES

PRESSURE SWITCH

Installation

The Potter PS120 Series Pressure Actuated Switches are designed primarily

to detect an increase and/or decrease from normal system pressure in

automatic fire sprinkler systems. Typical applications are: Wet pipe systems

with excess pressure, pressure tanks, air supplies, and water supplies. The

PS120 switch is factory set for 120 PSI (8,3 BAR) normal system pressure.

The switch marked with the word LOW is set to operate at a pressure decrease

of 10 PSI (0,7 BAR) at 110 PSI (7,6 BAR). The switch marked with the

word HIGH is set to operate at a pressure increase of 10 PSI (0,7 BAR) at

130 PSI (9 BAR). See section heading Adjustments and Testing if other

than factory set point is required.
1. Connect the PS120 to the system side of any shutoff or check valve.

2. Apply Teflon tape to the threaded male connection on the device.

(Do not use pipe dope)

3. Device should be mounted in the upright position.

(Threaded connection down)

4. Tighten the device using a wrench on the flats on the device.
Wiring Instructions

1. Remove the tamper resistant screw with the special key provided.

2. Carefully place a screwdriver on the edge of the knockout and sharply

apply a force sufficient to dislodge the knockout plug. See Fig. 9

3. Run wires through an approved conduit connector and affix the

connector to the device. A NEMA-4 rated conduit fitting is required

for outdoor use.

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada: 888-882-1833

• www.pottersignal.com

Service Use:

Automatic Sprinkler

NFPA-13

One or two family dwelling

NFPA-13D

Residential Occupancy up to four stories

NFPA-13R

National Fire Alarm Code

NFPA-72

(UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA

Accepted, CE Marked Pending)
Dimensions:
3.78" (9.6cm)W x 3.20" (8.1cm)D x 4.22" (10.7cm)H

Enclosure: Cover- Die-cast with textured red powdercoat finish, single

cover screw and rain lip.

Base- Die-cast

Pressure Connection: Nylon 1/2" NPT male

Cover incorporates tamper resistant fastener that requires a

special key for removal. One key is supplied with each device.

For optional cover tamper switch kit, order Stock No. 0090200.

See bulletin #5401200 PSCTSK.

Switch Contacts: SPDT (Form C)

10.1 Amps at 125/250VAC, 2.0 Amps at 30VDC

One SPDT in PS120-1, Two SPDT in PS120-2
Environmental Specifications:

NEMA 4/IP55 Rated Enclosure - indoor or outdoor when used

with NEMA 4 conduit fittings.

Temperature range: -40°F to 140°F (-40°C to 60°C)

Pressure Range: 25-175 PSI (1,7 - 12,1 BAR)
Differential: Typical 2 lbs. at 25 PSI (0,14 at 1,7 BAR)

8 lbs at 175 PSI (55 at 12,1 BAR)

Maximum System Pressure: 300 PSI (20,68 BAR)

Factory Adjustment:

PS120-1 operates on decrease at 110 PSI (7,6 BAR)

PS120-2 operates in increase at 130 PSI (9 BAR) and

on decrease at 110 PSI (7,6 BAR)

Conduit Entrance:

Two knockouts provided for 1/2" conduit. Individual

switch compartments and ground screw suitable for

dissimilar voltages

Tamper:

4. Connect the wires to the appropriate terminal connections for the

service intended. See Figures 2,4,5,6, and 8. See Fig. 7 for two switch

one conduit wiring.
Adjustment And Testing

The operation of the pressure supervisory switch should be tested upon

completion of installation and periodically thereafter in accordance with

the applicable NFPA codes and standards and/or the authority having

jurisdiction (manufacturer recommends quarterly or more frequently).

Note: Testing the PS120 may activate other system connected devices.

The use of a Potter BVL (see product bulletin 8900067 for details) is

recommended to facilitate setting and testing of the PS120 pressure switch.

When a BVL (bleeder valve) is used, the pressure to the switch can be

isolated and bled from the exhaust port on the BVL without effecting the

supervisory pressure of the entire system. See Fig. 3

The operation point of the PS120 Pressure Switch can be adjusted to any

point between 25 and 175 PSI (1,7 - 12,1 BAR) by turning the adjustment

knob(s) clockwise to raise the actuation point and counter clockwise to

lower the actuation point. In the case of the PS120-2, both switches operate

independent of each other. Each switch may be independently adjusted to

actuate at any point acrosss the switch adjustment range. Initial adjustment

can be made with a visual reference from the top of the adjustment knob

across to the printed scale on the switch bracket. Final adjustments should

be verified with a pressure gauge.

Ordering

Information

Model

Description Stock

No.

PS120-1

Pressure switch with one set 1341203

SPDT contacts

PS120-2

Pressure switch with two sets 1341204

SPDT contacts

Hex Key 5250062

Cover Tamper Switch Kit 0090200

BVL

Bleeder valve 1000018