Vsr-sg – Potter Releasing Systems User Manual

Page 96

Advertising
background image

96

PRINTED IN USA

PAGE 2 OF 4

MFG. #5401205 - REV G

9/09

VSR-SG

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

AND GLUE-IN UNION

FOR CPVC PIPE

Do not trim the paddle. Failure to follow these instructions may prevent the

device from operating and will void the warranty.

Do not over-tighten the union nut, hand tighten only.

Installation (see Fig. 1, 2, and 3)

These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they

will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24"

(60 cm) of a valve or drain. The unit has a 1" male fitting for gluing into a CPVC plastic tee.
NOTE: Do not leave cover off for an extended period of time.
Loosen the union nut and separate the 1" male fitting from the VSR-SG. Glue the 1" male fitting into the TEE following the TEE manufacturer's

instructions for preparation and gluing of CPVC piping systems. (Note: The 1" male fitting must bottom out on the stop of the TEE for proper

operation of the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before attaching the VSR-SG to the 1" male fitting. Select the proper

paddle for the pipe size and type of TEE used. See Fig. 3 for instructions on how to change paddle. Verify that the o-ring is properly positioned in

its groove. Hand tighten the nut on the union after orienting the device in the appropriate direction to detect waterflow as shown in Fig. 2.
The vane must not rub the inside of the TEE or bind in any way. The stem should move freely when operated by hand.

Fig. 2

Important:

11 paddles are furnished with each unit

to accommodate the various sizes and

manufacturers of TEES. The paddles have

raised lettering that show the pipe size and

the TEE manufacturer they are to be used

with. The proper paddle must be used. The

paddle must be properly attached (see Fig. 3)

and the screw that holds the paddle must be

securely tightened.

Fig. 1

Retard Adjustment

The delay can be adjusted by rotating the retard

adjustment knob from 0 to the max setting (60-90

seconds). The time delay should be set at the

minimum required to prevent false alarms.

Glue the 1" male fitting into the TEE following

the TEE manufacturer's instructions for

preparation and gluing of CPVC piping

systems. Wait 2 to 4 hours to allow the glue

to dry before attaching the VSR-SG to the 1"

male fitting.

Fig. 3

OPTIONAL COVER TAMPER SWITCH

DWG# 1205-1A

RETARD

ADJUSTMENT

KNOB

Insure that O-ring is in O-ring groove before

installing switch.

MOUNT SO ARROW

ON BASE POINTS

IN DIRECTION OF

WATERFLOW

1" MALE FITTING

ON ALL SIZES

Do not leave cover off for extended period of time

RUN OF THE TEE

MAY BE

1”, 1 ¼”, 1

½”, or 2”

Flowing water activates device in

one direction only.

Advertising
This manual is related to the following products: