Wet System With Excess Pressure

(Waterflow With Pressure Supervision)

Fig. 6

TO EXCESS

PRESSURE

PUMP

CHEC

K

RBV

S

EXCESS

PRESSURE

SUPERVISION

PS120-1

PS120-2

BVL

BLEEDER

VALVE

(OPEN)

CITY WATER

PRESSURE

GAUGE

TAMPER

DEVICE

OSYSU

(OPEN)

OSY CONTROL

VALVE (OPEN)

WATER PRESSURE

FROM CITY MAINS

CHECK

RISER TO

SPRINKLER

HEADS

WATER BY-PASS

TEST VALVE

(CLOSED)

WATERFLOW SWITCH

(NO RETARD)

PS10-1

PS10-2

RBVS

STRAINER

DRAIN

VALVE

(CLOSED)

TO WATER

MOTOR GONG

DRIP

CUP

CHECK

VALVE

DRAIN

PIPE

DWG# 8704200-F1

Unless excess pressure is pumped into system, the waterflow device should have a retard per NFPA 72 2010

17.12. There shall be no shut-off valve in line to a pressure type waterflow switch, unless the shut-off is electri-

cally supervised. Per NFPA 72 2010 23.8.5.10.4, the Potter Model RBVS is designed to electrically supervise

ball valves.