Bells, Pba-ac & mba-dc – Potter Releasing Systems User Manual

Page 66

Advertising
background image

66

Size inches

(mm)

Voltage

Model

Number

Stock

Number

Current

(Max.)

Typical dB at

10 ft. (3m) (2)

Minimum dB at

10 ft. (3m) (1)

6 (150)

12VDC

MBA126

1750070

.12A

85

76

8 (200)

12VDC

MBA128

1750080

.12A

90

77

10 (250)

12VDC

MBA1210

1750060

.12A

92

78

6 (150)

24VDC

MBA246

1750100

.06A

87

77

8 (200)

24VDC

MBA248

1750110

.06A

91

79

10 (250)

24VDC

MBA2410

1750090

.06A

94

80

6 (150)

24VAC

PBA246

1806024*

.17A

91

78

8 (200)

24VAC

PBA248

1808024*

.17A

94

77

10 (250)

24VAC

PBA2410

1810024*

.17A

94

78

6 (150)

120VAC

PBA1206

1806120*

.05A

92

83

8 (200)

120VAC

PBA1208

1808120*

.05A

99

84

10 (250)

120VAC PBA12010 1810120*

.05A

99

86

All DC bells are polarized and have built-in transient protection.

* Does not have ULC listing.

BELLS

PBA-AC & MBA-DC

These vibrating type bells are designed for use as fire, burglar or general

signaling devices. They have low power consumption and high decibel

ratings. The unit mounts on a standard 4" (101mm) square electrical box

for indoor use or on a model BBK-1 weatherproof backbox or BBX-1

deep weatherproof backbox for outdoor applications. Weatherproof

backbox model BBK-1, Stock No. 1500001.

PRINTED IN USA

PAGE 1 OF 2

MFG. #5400776 - REV Y

5/08

UL, ULC, and FM Approved

Sizes Available: 6" (150mm), 8" (200mm) and 10" (250mm)

Voltages Available:

24VAC

120VAC

12VDC (10.2 to 15.6) Polarized

24VDC (20.4 to 31.2) Polarized

Service Use:

Fire Alarm

General Signaling

Burglar Alarm

Environment: Indoor or outdoor use (See Note 1)

-40° to 150°F (-40° to 66°C)

(Outdoor use requires weatherproof backbox.)

Termination:

AC Bells - 4 No. 18 AWG stranded wires

DC Bells - Terminal strip

Finish: Red powder coating

Optional: Model BBK-1 weatherproof backbox

Model BBX-1 deep weatherproof backbox

Potter Electric Signal Company, LLC • St. Louis, MO, • Phone: 866-572-3005/Canada 888-882-1833

• www.pottersignal.com

In outdoor or wet installations, bell must be mounted with

weatherproof backbox, BBK-1 or BBX-1. Standard electrical boxes

will not provide a weatherproof enclosure. If the bell and/or assembly

is exposed to moisture, it may fail or create an electrical hazard.

Notes:

1. Minimum dB ratings are calculated from integrated sound pressure

measurements made at Underwriters Laboratories as specified in UL

Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C).

2. Typical dB ratings are calculated from measurements made with a

conventional sound level meter and are indicative of output levels in

an actual installation.

3. ULC only applies to MBA DC bells.

*