Switch Terminal Connections

Clamping Plate Terminal

Fig. 4

Fig. 3

Retard Adjustment:

To change time turn knob (either

direction) for desired time delay.

Use the minimum amount of retard

necessary to prevent false alarms, a

“B” setting is usually adequate for

this. Factory set at “B”.

APPROX. RETARD SETTINGS (IN SEC.)

0 A

B

C

D

E

0

10-25

20-40

35-55

50-70

60-90

OUTGOING

INCOM

ING

DWG# 923-3

Fig. 5 Typical Wet System

DO NOT LEAVE COVER

OFF FOR EXTENDED

PERIOD OF TIME

DWG# 987-30

An uninsulated section of a single conductor

should not be looped around the terminal and

serve as two separate connections. The wire must

be severed, thereby providing supervision of the

connection in the event that the wire becomes

dislodged from under the terminal.

Use teflon tape sealant only. Apply only

to male threads of connectors.
Use of pipe cement voids warranty as this

material may obstruct pressure aperture

resulting in loss of alarm signal.
Device must be installed before any shut

off valve on alarm port line unless it is

supervised by a supervisory switch such

as Potter Model RBVS.
The system should be tested on a

quarterly basis or more frequently to

insure proper operation.

Due to the possibility of unintended discharges caused by pressure

surges, trapped air, or short retard times, waterflow switches that

are monitoring wet pipe sprinkler systems shall not be used as

the sole initiating device to discharge AFFF, deluge, or chemical

suppression systems.

ALARM CHECK VALVE

RISER TO

SPRINKLER

HEADS

OPTION 1

OPTION 2

WFSR-F

WATERFLOW

DEVICE

WITH RETARD

PS10

WATERFLOW

PRESSURE SWITCH

TO WATER

MOTOR GONG

SHUTOFF

(OPEN)

PETCOCK

(OPEN)

ALARM LINE

SHUTOFF VALVE,

SUPERVISED

(OPEN)

WATER PRESSURE GAUGE

(SYSTEM PRESSURE)

(OPEN)

CHECK VALVE

USE TO BUILD

SMALL EXCESS

SURGES

BY-PASS LINE

WATER PRESSURE GAUGE

(CITY PRESSURE)

(OPEN)

CHECK

RBVS

DRAIN

VALVE

(CLOSED)

WATER BY-PASS

TEST VALVE

(CLOSED)

OSYSU

TAMPER

DEVICE

OSY CONTROL VALVE

(OPEN)

RETARD

CHAMBER

PETCOCK

(OPEN)

DRIP

CUP

CHECK

VALVE

STRAINER

DWG. #8700023-2A

DRAIN

PIPE

WATER PRESSURE