Wfsr-f, Waterflow alarm switch with retard – Potter Releasing Systems User Manual

Page 105

Advertising
background image

105

WFSR-F

WATERFLOW ALARM SWITCH

WITH RETARD

MFG. #5400987 - REV W

12/08

PAGE 1 OF 2

PRINTED IN USA

Waterflow Alarm Switch With Retard For Supervision Of Wet

Alarm Check Valve

The Model WFSR-F is a pressure operated switch with an adjustable,

instantly recycling pneumatic retard to prevent false alarms due to water

pressure variation. The WFSR-F is connected into the alarm port of a wet

sprinkler system alarm check valve (see " WARNING", page 2).
Installation

A male ½" NPT pipe fitting is provided for connection to the alarm port

of the alarm check valve. No additional mounting or support is required.

UL, cUL and CSFM Listed, FM Approved and NYMEA

Accepted, CE Marked, VdS Approved

Dimensions: 5 9/16"H x 3 1/2"W x 5 7/8"D

(14,1cm H x 8,9cm W x 14,9cm D)

Weight: 1.5 lbs. (3,3 kg.)

Enclosure: Cover - Die-cast with textured red powdercoat finish

Base - Die-cast aluminum

Pressure Connection: 1/2" Male NPT

Pressure Adjustments:

Factory adjusted to operate between

5 and 8 PSI (0.35 and 0,55 BAR) on

rising pressure

Maximum system pressure: 175 PSI (12,1 BAR)

Contact Ratings: Two Sets of SPDT (Form C)

15.0 Amps at 125/250VAC

2.0 Amps at 30VDC Resistive

Conduit Entrances: Two knockouts provided for 1/2" conduit

Environmental Specifications: 40°F to 120°F (4,5°C to 49°C)

NEMA 4 Enclosure - when used

with proper conduit fittings

Service Use: Automatic Sprinkler

NFPA-13

One or two family dwelling

NFPA-13D

Residential occupancy up to four stories NFPA-13R

National Fire Alarm Code

NFPA-72

Tamper: Cover incorporates tamper resistant fasteners that require

a special key for removal. One key is supplied with each device. For

optional cover tamper switch kit, order Stock No. 0090018.

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada: 888-882-1833

• www.pottersignal.com

Fig. 2 Typical Electrical Connections

Note: For supervised circuits see “Switch Terminal Connections”

drawing and caution note (Fig. 4).

2 SETS OF NORMALLY

OPEN CONTACTS

CLOSE ON ALARM

THE N.C. AND N.O. MARKINGS ON

THE SWITCH ARE FOR AN ALARM

CONDITION.

THE CONTACTS ARE REVERSED

WHEN THE DEVICE IS IN THE

NORMAL CONDITION.

WATERFLOW ZONE

ON FIRE PANEL

EOLR FROM

FIRE PANEL

POSITIVE DC

OR HOT AC

NEGATIVE DC OR

NEUTRAL AC

DWG# 761-2

BELL

COM

NO

NC

COM

NO

NC

COM

NO

NC

COM

NO

NC

EOLR

Stock number - 1010080

This device is not intended for applications

in explosive environments.

Fig. 1 WFSR-F

TO SPRINKLERS

FROM WATER

SUPPLY

BY-PASS

TEST VALVE

RBVS

WFSR-F

TO

DRAIN

RETARD

CHAMBER

DWG# 987-1A

Allow 5" (12,7cm) to the front of the unit for removal of the cover. Install

with the pressure connection down.
Testing

Operation of the unit is checked by opening the by-pass test valve or

inspector's test valve. The frequency of the inspection and testing for the

Model WFSR-F and its associated protective monitoring system should

be in accordance with applicable NFPA Codes and Standards and/or

authority having jurisdiction (manufacturer recommends quarterly or

more frequently).