background image

73

PAGE 1 OF 4

PCVS-1, -2

CONTROL VALVE

SUPERVISORY SWITCH

PRINTED IN USA

MFG. #5400980 - REV V

5/09

UL, ULC, and CSFM Listed, FM Approved, NYMEA Accepted,

CE Marked

Dimensions: 4.75"L x 2.25"W x 8.2"H (stem extended)

12,1cm L x 5,7cm W x 18,3cm H

Weight: 1.35 lb. (0,61 kg.)

Enclosure: Cover - Die-cast

Finish - Red Spatter Enamel

Base - Die Cast Zinc

All parts have corrosion resistant finishes.

Cover Tamper: Tamper Resistant Screws,

Optional cover tamper switch kit available

Mounting: 1/2" NPT
Contact Rating: PCVS-1: One set of SPDT (Form C)

PCVS-2: Two sets of SPDT (Form C)

15 Amps at 125/250VAC

2.5 Amps at 30VDC resistive

Environmental Limitations: -40°F to +140°F (-40°C to 60°C)

NEMA 4 and NEMA 6P Enclosure (IP67) when used with

appropriate watertight conduit fittings.

Indoor or Outdoor Use (Not for use in hazardous locations. See

bulletin no. 5400694 PIVS-U-EX for hazardous locations.)

The Model PCVS is a weather proof and tamper resistant switch for

monitoring the open position of fire sprinkler control valves of the post

indicator, butterfly and other types. Depending on the model, one or

two SPDT (Form C) contacts are provided which will operate when the

valve position is altered from an open state.

The unit mounts in a 1/2" NPT tapped hole in the post indicator or

butterfly valve housing. The device is engaged by the indicating

assembly of the post indicator or the operating mechanism of the

butterfly valve, actuating switch(es) when the valve is fully open. The

unit should be installed where it is accessible for service.

The cover is held in place by two tamper resistant screws that require

a special tool to remove. The tool is furnished with each device and

should be left with the building owner or responsible party. Replacement

or additional cover screws and hex keys are available. See ordering

information.
Optional Cover Tamper Switch

A field installable cover tamper switch is available as an option which may

be used to indicate removal of the cover. See ordering information.
Testing

The PCVS and its associated protective monitoring system should be

tested in accordance with applicable NFPA codes and standards and/or

the authority having jurisdiction (manufacturer recommends quarterly

or more frequently).

Potter Electric Signal Company • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833

• www.pottersignal.com

Ordering Information

Model

Description

Stock No.

PCVS-1

Potter Control Valve Switch (single switch)

1010107

PCVS-2

Potter Control Valve Switch (double switch)

1010207

--

Cover Screw

5490424

--

Hex Key for Cover Screws and Installation Adjustments

5250062

PBK-S

Pratt Butterfly Valve Kit - Up to 12" (300mm)

0090133

PBK-L

Pratt Butterfly Valve Kit - 14" (355mm) and Up

0090132

PVK

Pratt Valve Kit

1000060

--

Optional Cover Tamper Switch Kit

0090131

KBK

Kennedy Butterfly Valve Kit

0090143

For pressure reducer type valve installation kits (if required) contact valve manufacturer.

Conduit Entrances: Two knockouts for 1/2" conduit provided.

Service Use:

Automatic Sprinkler

NFPA-13

One or two family dwelling

NFPA-13D

Residential occupancy up to four stories

NFPA-13R

National Fire Alarm Code

NFPA-72