Ps120 series, Pressure switch – Potter Releasing Systems User Manual

Page 85

Advertising
background image

85

MFG. #5400933 - REV D

1/08

PRINTED IN USA

PAGE 3 OF 3

PS120 SERIES

PRESSURE SWITCH

DWG# 928-4

Break out thin section of divider to provide path for wires

when wiring both switches from one conduit entrance.

One Conduit Wiring

Fig. 6

Fig. 8

DWG#928-5

Fig. 9

Removing Knockouts

C

C

C

1

2

C

1

2

LOW PRESSURE SWITCH

HIGH PRESSURE SWITCH

DWG# 930-3

Changing Pressure

Low Pressure Signal Connection

EOLR

TO FIRE ALARM PANEL

DWG# 928-1

EOLR

TO FIRE ALARM PANEL

DWG# 928-2

High Pressure Signal Connection

Fig. 5

Fig. 7

(With normal system pressure)

Engineer/Architect Specifications Pressure Type Waterflow Switch

Pressure type supervisory switches; shall be a Model PS120 as

manufactured by Potter Electric Signal Company, St. Louis, MO., and shall

be installed on the fire sprinkler system as shown and or specified herein.
Switches shall be provided with a ½" NPT male pressure connection to be

connected into the air supply line on the system side of any shut-off valve.
A Model BVL bleeder valve as supplied by Potter Electric Signal Company

of St. Louis, MO., or equivalent shall be connected in line with the PS120 to

provide a means of testing the operation of the supervisory switch. (See Fig. 3)
The switch unit shall contain SPDT (Form C) switch(es). One switch shall

be set to operate at a pressure decrease of 10 PSI (0,7 BAR) from normal.

If two switches are provided, the second switch shall be set to operate at a

pressure increase of 10 PSI (0,7 BAR) from normal.
Switch contact shall be rated at 10.1 Amps at 125/250VAC and 2.0 Amps

at 30VDC. The units shall have a maximum pressure rating of 300 PSI

(20,68 BAR) and shall be adjustable from 25 to 175 PSI (1,7 to 12,1 BAR).

• Installation must be performed by qualified personnel and in accordance with all national and

local codes and ordinances.

• Shock hazard. Disconnect power source before servicing. Serious injury or death could result.

• Read all instructions carefully and understand them before starting installation. Save

instructions for future use. Failure to read and understand instructions could result in improper

operation of device resulting in serious injury or death.

• Risk of explosion. Not for use is hazardous locations. Serious injury or death could result.

• Do not tighten by grasping the switch enclosure. Use wrenching flats on the

bushing only. Failure to install properly could damage the switch and cause

improper operation resulting in damage to equipment and property.

• To seal threads, apply Teflon tape to male threads only. Using joint compounds

or cement can obstruct the pressure port inlet and result in improper device

operation and damage to equipment.

• Do not over tighten the device, standard piping practices apply.

Terminal #1: Closed under

normal system pressure.
Terminal #2: Open under

normal system pressure,

closes on pressure drop. Use

for low pressure signal.

Terminal #1: Open under

normal system pressure, closes

on pressure increase. Use for

high pressure signal.
Terminal #2: Closed under

normal system pressure.