VSR-SG

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

AND GLUE-IN UNION

FOR CPVC PIPE

General Information

The Model VSR-SG is a vane type waterflow switch for use on wet

sprinkler systems using CPVC plastic fittings (manufactured by Tyco,

Nibco, Victaulic, Ipex, and Spears Manufacturing Company) that use 1”,

1 ¼”, 1 ½”, or 2” pipe sizes. It is equipped with a union to accommodate

installation in confined spaces.
The VSR-SG contains two single pole, double throw, snap action

switches and an adjustable, instantly recycling pneumatic retard. The

switches are actuated when a flow of 10 GPM (38 LPM) or more

occurs downstream of the device. The flow condition must exist for a

period of time necessary to overcome the selected retard period.

UL, CUL and CSFM Listed
Service Pressure:
Up to 175 PSI (12,07 BAR)
Flow Sensitivity Range for Signal:

4-10 GPM (15-38 LPM) - UL

Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)

10.0 Amps at 125/250VAC

2.0 Amps at 30VDC Resistive

10 mAmps min. at 24VDC

Conduit Entrances: Two openings provided for 1/2" conduit.

Individual switch compartments suitable

for dissimilar voltages.

Environmental Specifications:

• NEMA 4/IP54 Rated Enclosure suitable for indoor or

outdoor use with factory installed gasket and die-cast housing

when used with appropriate conduit fitting.

• Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL

Service Use:

Automatic

Sprinkler NFPA-13

One or two family dwelling

NFPA-13D

Residential occupancy up to four stories

NFPA-13R

National Fire Alarm Code

NFPA-72

Installation must be performed by qualified personnel and in

accordance with all national and local codes and ordinances.

• Shock hazard. Disconnect power source before servicing. Serious

injury or death could result.

• Risk of explosion. Not for use in hazardous locations. Serious

injury or death could result.

Specifications subject to change without notice.

Stock Number: 1144460
Optional: Cover Tamper Switch Kit, stock no. 0090148
Replaceable Components: Retard/Switch Assembly, stock no. 1029030

Enclosure

The VSR-SG switches and retard device are enclosed in a general

purpose, die-cast housing. The cover is held in place with two tamper

resistant screws which require a special key for removal. A field

installable cover tamper switch is available as an option which may

be used to indicate unauthorized removal of the cover. See bulletin

number 5401103 for installation instructions of this switch.

Waterflow switches that are monitoring wet pipe sprinkler systems shall

not be used as the sole initiating device to discharge AFFF, deluge,

or chemical suppression systems. Waterflow switches used for this

application may result in unintended discharges caused by surges,

trapped air, or short retard times.

Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-572-3005 • Tech Support: 866-956-0988 /Canada 888-882-1833

• www.pottersignal.com

Advertising