Lever type bleeder valve – Potter Releasing Systems User Manual

Page 68

Advertising
background image

68

BVL

LEVER TYPE BLEEDER VALVE

PRINTED IN USA

PAGE 1 OF 1

MFG. #5400799 - REV K

5/08

General Information

The Model BVL, lever type bleeder valve, is for use as a test valve for

pressure operated devices on wet pipe sprinkler systems that have excess

pressure, or dry pipe sprinkler systems.

The BVL should be installed in-line with the pressure device. It provides

a convenient means for removal or testing the pressure actuated device

without affecting the pressure in the system. Closing the valve (moving

the valve handle perpendicular to the 1/2" pipeline) shuts off the water

or air from the supply and opens a small orifice (pin-hole) to exhaust the

pressure between the valve and the pressure device. This should provide

a low pressure actuation of the pressure device, testing its operation.
Installation

The BVL should be installed in-line to the alarm or supervisory device

with the “PD” (Potter Device) stamp, or with the arrow pointing toward

the alarm or supervisory device that is to be tested.

Valve Body: Bronze

Handle: Zinc plated steel

Maximum Pressure: 300 PSI (20.7BAR)

Connections: 1/2" NPT

Exhaust Orifice: .125" (3mm)

Stock number - 1000018

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada: 888-882-1833

• www.pottersignal.com

PS40

BVL

RISER TO SPRINKLERS

DWG# 799-1

The BVL should be installed so the exhaust orifice is pointed in a

safe direction.

Advertising