VSR-SG

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

AND GLUE-IN UNION

FOR CPVC PIPE

Notes:

1. The Model VSR-SG has two switches, one can be used to operate a

central station, proprietary or remote signaling unit, while the other

contact is used to operate a local audible or visual annunciator.

2. For supervised circuits, see “Switch Terminal Connections”

drawing and warning note (Fig. 5).

Fig. 6 Typical Electrical Connections

Fig. 5 Switch Terminal Connections Clamping Plate Terminal

Fig. 4

Break out thin section of cover when wiring both switches from one

conduit entrance.

Testing

The frequency of inspection and testing for the Model VSR-SG and its associated protective monitoring system shall be in accordance with applicable

NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection

device on the system, application of the VSR-SG is not recommended or advisable.

A minimum flow of 10 GPM (38 LPM) is required to activate this device.

Advise the person responsible for testing of the fire protection system that this system must be tested in accordance

with the testing instructions.

Fig. 7 Mounting Dimensions

DWG. 1146-12

POWER SOURCE

SUITABLE FOR BELL

WATERFLOW ZONE

ON FIRE PANEL

EOLR

BELL

GREEN GROUND

SCREWS

Fig. 8

An uninsulated section of a single conductor should not be looped

around the terminal and serve as two separate connections. The

wire must be severed, thereby providing supervision of the

connection in the event that the wire become dislodged from under

the terminal. Failure to sever the wire may render the device

inoperable risking severe property damage and loss of life.
Do not strip wire beyond 3/8" of length or expose an uninsulated

conductor beyond the edge of the terminal block. When using

stranded wire, capture all strands under the clamping plate.

DWG# 1205-4

DWG# 1205-15

DWG# 1190-1

5.56 in

(141.2 mm)

PIPE

PLASTIC PADDLE

2.00 in

(50.8 mm)

3.91 in

(99.33 mm)

3.50 in

(89.0 mm)