FIG. 1

SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" SIZES

and smooth the edges of the groove to prevent damage to the valve

packing and to allow the trip rod to move easily in and out of the

groove as the valve is operated.

7. Mount the OSYSU with the trip rod centered in groove.
8. Final adjustment is made by loosening 2 screws (see Fig. 1) and

sliding the OSYSU on the bracket. Adjustment is correct when

switches are not activated with the trip rod seated in the valve stem

groove and that the switches activate when the trip rod moves out

of the groove.

9. Tighten the adjustment screws and all mounting hardware. Check

to insure that the rod moves out of the groove easily and that the

switches activate within one turn when the valve is operated from

the FULL OPEN towards the CLOSED position.

NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE

STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH

BEING ACTIVATED BY THE STEM THREADS COULD RESULT

IN A FALSE VALVE OPEN INDICATION.

SMALL VALVE INSTALLATION
1. Remove and discard "C" washer and roller from the trip rod.
2. With the valve in the FULL OPEN position, locate the OSYSU

across the valve yoke as far as possible from the valve gland, so

that the trip rod lays against the non-threaded portion of the valve

stem.

3. Loosen the locking screw that holds the trip rod in place and adjust

the rod length (see Fig. 4). When adjusted properly, the rod should

extend past the valve screw, but not so far that it contacts the clamp

bar. Tighten the locking screw to hold the trip rod in place.

NOTE: If trip rod length is excessive, loosen the locking screw

and remove the trip rod from the trip lever. Using pliers, break off

the one (1) inch long notched section (see Fig. 5). Reinstall trip rod

and repeat Step 3 procedure.

4. Mount the OSYSU loosely with the carriage bolts and clamp bar

supplied. On valves with limited clearance use J-hooks supplied

instead of the carriage bolts and clamp bar to mount the OSYSU.

5. Mark the valve stem at the center of the trip rod.
6. Remove the OSYSU. File a 1/8" deep groove centered on the mark

on the valve stem utilizing a 3/16" diameter straight file. Round

CLAMP

BAR

CARRIAGE

BOLT

DWG# 979-3

BRACKET

SLOTTED

MOUNTING

HOLES MAY BE

USED FOR FINE

ADJUSTMENT OF

SWITCH ON

BRACKET

These switches mount conveniently to most 2" to 12" OS&Y valves. They will mount on some valves as small as 1/2". J-hooks

may be required on valves with limited clearance.

Advertising
This manual is related to the following products: