Ps120 series, Pressure switch – Potter Releasing Systems User Manual

Page 84

Advertising
background image

84

MFG. #5400933 - REV D

1/08

PRINTED IN USA

PAGE 2 OF 3

PS120 SERIES

PRESSURE SWITCH

Typical Sprinkler Applications

Switch Clamping Plate Terminal

Dimensions

OUTGOING

INCOM

ING

DWG# 923-3

Closing of any shutoff valves between the alarm check valve and

the PS10 will render the PS10 inoperative. To comply with NFPA-

72 any such valve shall be electrically supervised with a

supervisory switch such as Potter Model RBVS.

Fig. 1

Fig. 2

Fig. 3

PS120

SUPERVISORY

PRESSURE

SWITCH

BLEEDER

TEST

VALVE

BVL

WET SYSTEM

ALARM CHECK

VALVE

PS10

WATERFLOW

ALARM

SWITCH

WATER

MOTOR

GONG

RBVS

RBVS

CHECK

VALVE

EXCESS

PRESSURE

PUMP

OS & Y

VALVE

WATER

BY-PASS

TEST VALVE

RBVS

DWG #926-1A

Typical Connections
Fig. 4

An uninsulated section of a single conductor

should not be looped around the terminal and

serve as two separate connections. The wire

must be severed, thereby providing supervision

of the connection in the event that the wire

becomes dislodged from under the terminal.

NOTE: To prevent leakage, apply Teflon tape sealant to male threads only.

2.87

[72.97]

4.22

[107.19]

2.48

[62.87]

3.78

[95.89]

3.20

[81.28]

1.60

[40.64]

GROUND

SCREWS

DWG# 930-1

1/2" NPT

ADJUSTMENT

KNOB

COM

1

2

EOLR

TO FIRE

ALARM

PANEL

TO FIRE

ALARM

PANEL

EOLR

COM

1

2

2

1

COM

HIGH

AIR

LOW

AIR

PS120-1

PS120-2

WITH NORMAL SYSTEM

PRESSURE APPLIED LOW -

TERMINAL 2 CLOSES ON

PRESSURE DROP.

WITH NORMAL SYSTEM

PRESSURE APPLIED

HIGH - TERMINAL

1 WILL CLOSE ON

PRESSURE INCREASE.

DWG# 933-1