Determine Fire Alarm Requirements
NFPA 101 Life Safety Code determines the fire alarm requirements based on the occupancy rating of the building.
Within each occupancy chapter, section 3.4 will specify the fire alarm requirements for that occupancy class.

Section 3.4 is “Detection, Alarms & Communication”. Section 3.5 is “Extinguishing Requirements”.

Section 3.4 Detection, Alarms and Communication
The General Provision

Specifies the conditions under which a fire alarm is required in that particular occupancy.

The Initiation Provision

Specifies how the fire alarm will be activated, other than as relates to automatic fire detection. It is typical in

many occupancy chapters that the Initiation provision call for “Manual activation in accordance with 9.6.2.1”.

When referred to chapter 9, only the applicable portions of chapter 9 apply for that occupancy.

The Notification Provision

Specifies “On Premises” signaling requirements. It may require voice evacuation, and may permit or prohibit

the use of “Pre-Signal” features.

The Detection Provision

Specifies requirements for automatic detection.This section should always be reviewed, even if the building is

not required to have a fire alarm system under the general statement for that occupancy class.

The Emergency Forces Notification Provision

Includes any requirement for “Off Premises” signaling (monitoring).

Section 3.5 Extinguishing Requirements
Specifies requirements for automatic sprinkler systems. Refers to chapter 9 section 9-7 “Automatic Sprinklers

and other Extinguishing Equipment”
The code may require either an, approved automatic sprinkler or an approved supervised automatic sprinkler.

Where a supervised automatic sprinkler is required, NFPA 101 2009 9-7.2.1 and 9-7.2.2 are applicable.

Sprinkler System Supervision Includes:

Water flow

Water Supply Control Valves

Fire Pump Status

Water Tank, Levels and Pressures

Air Pressure on Dry Pipe Systems

Building Temperature

Water supply control valves shall be supervised to obtain a distinctive signal when in an off normal position,

within 2 revolutions of the handwheel, or when the valve has moved one fifth from its normal position.
The switch shall not restore to a normal condition throughout the entire travel of the valve, until it is restored to

a fully open position.
A Supervisory signal must be visually or audibly distinctive from both Alarm and Trouble signals.
Water flow and supervisory devices cannot be connected on the same initiating circuit so that the closing of a

valve is annunciated as a “trouble” condition.