Vsr-sg – Potter Releasing Systems User Manual

Page 98

Advertising
background image

98

PRINTED IN USA

PAGE 4 OF 4

MFG. #5401205 - REV G

9/09

VSR-SG

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

AND GLUE-IN UNION

FOR CPVC PIPE

Removal of Waterflow Switch
To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are

removed or replaced.

• Turn off electrical power to the detector, then disconnect wiring.
• Loosen nuts and seperate unit from the glued-in fittings
• Gently lift the unit far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift

the waterflow detector.

• Lift detector clear of pipe.

Fig. 9

Retard/Switch Assembly Replacement (See Fig. 9)

The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the

pipe

1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
2. Disconnect the power source for local bell (if applicable).
3. Identify and remove all wires from the waterflow switch.
4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
5. Remove the retard assembly by lifting it straight up over the tripstem.
6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
7. Re-install the (2) original mounting screws.
8. Reconnect all wires. Perform a flow test and place the system back in service.

Maintenance

Inspect detectors monthly. If leaks are found, replace the detector. The VSR-SG waterflow switch should provide years of trouble-free service.

The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order

replacement retard switch assembly stock #1029030 (see Fig. 6). There is no maintenance required, only periodic testing and inspection.

DWG# 1190-2

BREAK OUT THIN SECTION OF COVER

WHEN WIRING BOTH SWITCHES

FROM ONE CONDUIT ENTRANCE.

DO NOT REMOVE

(2) RETARD HOUSING

SCREWS

REMOVE (2) ORIGINAL MOUNTING

SCREWS HOLDING RETARD/SWITCH

ASSEMBLY TO BASE

RETARD/SWITCH ASSEMBLY

(2) ORIGINAL MOUNTING

SCREWS

(2) LOCATING PINS

(2) LOCATING PIN

BOSSES IN BASE

BASE

Advertising
This manual is related to the following products: