Vane type waterflow alarm switch with retard, Fig. 1 compatible pipe/ installation requirements – Potter Releasing Systems User Manual

Page 89

Advertising
background image

89

PRINTED IN USA

PAGE 89 OF 4

VSR

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

MFG. #5401146 - REV L

3/09

Do not trim the paddle. Failure to follow these instructions may prevent the

device from operating and will void the warranty.

Installation (see Fig. 1)

These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they

will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24"

(60 cm) of a valve or drain.

NOTE: Do not leave cover off for an extended period of time.
Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other

material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend

or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive

bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque

(see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way.

ADAPTER

USE (2) 5180162 ADAPTERS AS SHOWN ABOVE

DN50 ONLY

ADAPTER

50mm

20mm ±2mm MAX.

DWG# 1146-1F

Fig. 1

Compatible Pipe/ Installation Requirements

Model

Nominal Pipe

Size

Nominal Pipe

O.D.

Pipe Wall Thickness

Hole Size

U-Bolt Nuts

Torque

Schedule 10 (UL) Schedule 40 (UL)

BS-1387 (LPC)

DN (VDS)

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

ft-lb

n-m

VSR-2

2

DN50

2.375

60.3

0.109

2.77

0.154

3.91

0.142

3.6

0.091

2.3

1.25 + .125/-.062

33.0 ± 2.0

20

27

VSR-2 1/2

2.5

-

2.875

73.0

0.120

3.05

0.203

5.16

-

-

-

-

VSR-2 1/2

-

DN65

3.000

76.1

-

-

-

-

0.142

3.6

0.102

2.6

VSR-3

3

DN80

3.500

88.9

0.120

3.05

0.216

5.49

0.157

4.0

0.114

2.9

2.00 ± .125

50.8 ± 2.0

VSR-3 1/2

3.5

-

4.000

101.6

0.120

3.05

0.226

5.74

-

-

-

-

VSR-4

4

DN100

4.500

114.3

0.120

3.05

0.237

6.02

0.177

4.5

0.126

3.2

VSR-5

5

-

5.563

141.3

0.134

3.40

0.258

6.55

-

-

-

-

VSR-6

6

DN150

6.625

168.3

0.134

3.40

0.280

7.11

0.197

5.0

0.157

4.0

VSR-8

8

DN200

8.625

219.1

0.148

3.76

0.322

8.18

0.248

6.3

0.177

4.5

NOTE: For copper or plastic pipe use Model VSR-CF.

Retard Adjustment

The delay can be adjusted by rotating the retard adjustment knob from

0 to the max setting (60-90 seconds). The time delay should be set at

the minimum required to prevent false alarms

(Flowing water activates

device in one direction only.)

DO NOT LEAVE COVER OFF FOR

AN EXTENDED PERIOD OF TIME

TIGHTEN NUTS

ALTERNATELY

MOUNT ON PIPE SO

ARROW ON SADDLE

POINTS IN DIRECTION

OF WATERFLOW

ROLL PADDLE IN

OPPOSITE DIRECTION

OF WATERFLOW

DIRECTION OF

WATERFLOW

Hole must be drilled perpendicular to the pipe and vertically centered.

Refer to the Compatible Pipe/Installation Requirements chart for size.

Correct

Incorrect