Other field bus configurations

The following field buses are optionally available for the EL-FLOW Prestige instruments. For all mentioned field bus systems the EL-

FLOW Prestige instruments serve as slaves on the master/slave bus system. There is no mutual communication between slaves,

only between master and slave.

PROFIBUS DP

PROFIBUS DP is a 2-wire, RS485-based industrial data communication standard (field bus) which allows automation components

(like sensors, actuators and controllers) to exchange information. For more information regarding the PROFIBUS DP interface refer

to document 9.17.025.

DeviceNet

TM

The DeviceNet

TM

interface offers direct connection to a DeviceNet

TM

network according to the Mass Flow Controller Profile

specified by the ODVA. The Bronkhorst DeviceNet

TM

instrument is a Group 2 Only Server device which messages comply with the

Controlled Area Network (CAN) 2.0A standard and with the DeviceNet

TM

protocol. See document 9.17.026 for more information

about the DeviceNet

TM

interface.

EtherCAT®

Ethernet for Control Automation Technology (EtherCAT

®

) is an open high performance Ethernet-based field bus

system. The

EtherCAT® interface is described in more detail in document 9.17.063.

PROFINET

The PROFINET interface is 100% Ethernet-compatible and is used for data exchange between IO controllers (PLC, etc.)

and IO devices (slaves, field devices). PROFINET uses the proven communication model and application view of

PROFIBUS DP.

Refer to document 9.17.095 for more information.

3.6.1

Hook-up

See the following documents for hook-up diagrams and instructions for setting up bus communication with the following

communication interfaces:

PROFIBUS DP interface: hook-up diagram 9.16.121 and manual 9.17.025
DeviceNet

TM

interface: hook-up diagram 9.16.122 and manual 9.17.026

EtherCAT® interface: hook-up diagram 9.16.124 and manual 9.17.063
PROFINET interface: hook-up diagram 9.16.147 and manual 9.17.095

3.6.2

Baud rate, node address and parity setup

In the table below for the supported configurations for PROFIBUS DP, DeviceNet

TM

, EtherCAT® and PROFINET are shown. The

default selections are presented in bold.

Mode:

Digital

Connector:

9-pin D-sub (female)

5-pin M12 (male)

2x RJ45 (in/out)

2x RJ45

Interface/medium:

RS485

RS485

Ethernet

Ethernet

Protocol:

PROFIBUS DP

DeviceNet

TM

EtherCAT®

PROFINET

Baud rate:

Autodetect

(9600)

(19200)

(45450)

(93750)

(187500)

(500000)

(1500000)

(3000000)

(6000000)

(12000000)

125000

250000

500000

100000000

100000000

Node address:

0…126

0...63

0 (n/a)

0 (n/a)

Parity:

Even

None

None

None

PROFIBUS DP, DeviceNet

TM

, EtherCAT® and PROFINET communication options