Bronkhorst EL-FLOW Prestige User Manual

Page 40

Advertising
background image

Bronkhorst High-Tech B.V.

EL-FLOW Prestige

9.17.084

40

Alarm Delay Time

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

0…255

182

97/7

0x0C27/3112

This value represents the time in seconds the alarm action will be delayed when an alarm limit has been exceeded. This value also

delays the alarm off action if an alarm limit is no longer exceeded. Default value = '0'.

Alarm Maximum Limit

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned int

RW

0…32000

116

97/1

0x0C21/3106

Maximum limit for the ‘

8

Measured Value’ to trigger the maximum alarm situation (after ‘

182

Alarm Delay Time’). Range 0…32000

represents 0…100% signal. The ‘

116

Alarm Maximum Limit’ value must be greater than the ‘

117

Alarm Minimum Limit’ value. Default

value = '0'.

Alarm Minimum Limit

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned int

RW

0…32000

117

97/2

0x0X22/3107

Minimum limit for the ‘

8

Measured Value’ to trigger the minimum alarm situation (after ‘

182

Alarm Delay Time’). Range 0…32000

represents 0…100% signal. The ‘

117

Alarm Minimum Limit’ value must be smaller than the ‘

118

Alarm Maximum Limit’ value. Default

value = '0'.

Alarm Setpoint Mode

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

0…1

120

97/5

0x0C25/3110

Value 0: No setpoint change at alarm (default)
Value 1: New setpoint at alarm enabled (set at value ‘

121

Alarm New Setpoint’)

Alarm New Setpoint

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned int

RW

0…32000

121

97/6

0x0C26/3111

New (safe) setpoint during an alarm until reset. Range 0…32000 represents 0…100% setpoint. Default value = '0'.

Reset Alarm Enable

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

0…15

156

97/9

0C029/3114

Available alarm reset options (convert value to binary number to see which bits are active):

Bit

Low (0)

High (1)

Description

0

Off

On

Reset by micro switch

1

Off

On

External reset (not used)

2

Off

On

Reset by parameter ‘Reset’

3

Off

On

Automatic reset (when alarm conditions no longer apply)

Alarm reset options

Default value: value 15, all conditions above are enabled.