Bronkhorst EL-FLOW Prestige User Manual

Page 44

Advertising
background image

Bronkhorst High-Tech B.V.

EL-FLOW Prestige

9.17.084

44

When the controller output is used for pump or external valve steering (Mass Flow Meters only), make sure the

231

Valve Maximum’ is set to 0.3 [A]. For Mass Flow Controllers, the controller output is limited to a value below

10 Vdc due to the maximum valve current restriction.

C3A

Digital output, min/max alarm

During a min/max alarm, pin 5 is pulled down to 0 Vdc.

C4A

Digital output, counter alarm

During a counter alarm, pin 5 is pulled down to 0 Vdc.

C5S

Digital output, enabled by setpoint (for shut-off control)

Pin 5 is pulled down to 0 Vdc at a controller setpoint, e.g. for shut-off valve activation.

For factory selected analog control (…-A#-C5S):

When the ‘

12

Control Mode’ is set for analog control by factory, the minimum setpoint at which the device (shut-

off valve) connected to pin 5 is activated is 1.9%, to avoid that possible noise on the analog input does accidentally

activate the device.

For factory selected digital control (…-D#-C5S):

When the ‘

12

Control Mode’ is set for digital control by factory, the setpoint threshold for activating the device

connected to pin 5 is any value > 0.

Note: If the instrument is forced into ‘Valve Safe State’, the digital output is not affected, so a (n.c.) shut-off valve

connected to pin 5 will not close when the (n.c.) controller is in ‘Valve Safe State’.

Make sure to use 24Vdc power supply corresponding to the shut-off valve specifications. Cable 7.03.572 (T-part 9-

pin D-sub/loose end) or 7.03.603 (T-part 9-pin D-sub/DIN43650C) can be used for this operating option.

Example for -C5S- or -C0I- hook-up

C0I

Digital output, high/low switch via remote parameter (for shut-off control)

Pin 5 is pulled down to 0 Vdc when writing value 1 to parameter ‘

288

IO Switch Status’, this is undone by writing

value 0.

A device connected to pin5 (e.g. a shut-off valve) can be activated/de-activated by writing the parameter ‘

288

IO

Switch Status’.

Note: If the instrument is forced into ‘Valve Safe State’, the digital output is also affected, so a (n.c.) shut-off valve

connected to pin 5 will be closed when the (n.c.) controller is in ‘Valve Safe State’.

Make sure to use 24Vdc power supply corresponding to the shut-off valve specifications. Cable 7.03.572 (T-part 9-

pin D-sub/loose end) or 7.03.603 (T-part 9-pin D-sub/DIN43650C) can be used for this operating option.

D9E

Digital frequency output, measure

Measurement value is translated to a frequency within given frequency range.

The default frequency range to represent 0…100% flow is 0…10000 Hz. Any other frequency range must be

specified on order.

F9B

Digital pulse output, batch counter

Pin 5 is pulled down to 0 Vdc when a given batch size is reached (during a given pulse length).

By default, a pulse is given at each 1x the ‘

128

Counter Unit’ batch value, with a pulse length of 1 s. For instance,

when the ‘

128

Counter Unit’ is set to l

n

, a pulse is given each time 1 l

n

has passed through the instrument. An

Advertising