Field bus operation, Flow-bus master/slave controller operation, Changing baud rate, node address and parity – Bronkhorst EL-FLOW Prestige User Manual

Page 42: 3 field bus operation, 1 flow-bus master/slave controller operation, 2 changing baud rate, node address and parity

Advertising
background image

Bronkhorst High-Tech B.V.

EL-FLOW Prestige

9.17.084

42

4.3

Field bus operation

4.3.1

FLOW-BUS master/slave controller operation

EL-FLOW Prestige instruments offer possibilities for master/slave control via FLOW-BUS. The output value of any instrument

connected to FLOW-BUS is automatically available to all other instruments (without extra wiring). To setup master/slave control the

12

Control Mode’ of the instrument can be set to ‘FLOW-BUS Slave’ (value 2) or to ‘FLOW-BUS Analog Slave’ (value 13), depending

on how the ‘

139

Slave Factor’ should be set. Via the parameter ‘

158

Master Node’ the master device for the instrument is set. It is

possible to have multiple masters and slaves in a FLOW-BUS system. A slave instrument can also be a master for other instruments.

Setpoints from master instruments can be received via FLOW-BUS only. The parameters for master/slave control can

be changed through both RS232 and FLOW-BUS.

Master Node

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

1…125

158

33/14

0x042E/1071

Set the master node for the instrument.

Slave Factor

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Float

RW

0…500

139

33/1

0x0421/1058

The controller output from the master instrument is multiplied by the ‘

139

Slave Factor’/100% to get the slave instrument setpoint.

Example: if a master output is 80% and the ‘

139

Slave Factor’ value = 50, then the slave instrument setpoint is 80% x 50%/100% =

40%.

4.3.2

Changing baud rate, node address and parity

Any changes made to the instrument communication settings will not be restored after a factory reset. See section

5.2 for more details.

Top connector communication

Change the node address of the instrument by using the instructions for the applicable field bus in chapter 3. Change the baud rate

or parity of the installed field bus (top connector) with the following parameters using the RS232 interface:

Fieldbus 1 baudrate

Type

Access

Range

FlowDDE

FLOW

-BUS

Modbus

Unsigned long

RW

0…10000000000

201

125/9

0xFD48...0xFD49/64841...64842

For the accepted values see the applicable field bus in chapter 3.

Fieldbus 1 parity

Type

Access

Range

FlowDDE

FLOW-BUS

Modbus

Unsigned char

RW

0…2

335

125/12

0x0FAC/4013

The following values are accepted:

0 – no parity

1 – odd parity

2 – even parity