9.2 First-in First-out Function (FINFOUT)

9-4

9.2 First-in First-out Function (FINFOUT)

[Outline]

This is a first-in first-out type block data transfer function. The FIFO data table is composed of a 4-
word header part and a data buffer. 3 words of the header part (data size, input size, output size) must
be set before this function is referenced.

When the data input command (In-Cmd) becomes ON, the designated number of data is

sequentially stored from the designated input data area to the data area of the FIFO table.

When the data output command (Out-Cmd) becomes ON, the designated number of data are

transferred from the head of the data area of the FIFO table to the designated output data area.

When the reset command (Reset) becomes ON, the number (amount) of data stored is set to zero

and the FIFO table empty output (Tbl-Emp) becomes ON.

If "size of available space for data (empty size) < input size" or if "data size < output size," the

FIFO table error (Tbl-Err) becomes ON.

[Format]

Symbol : FINFOUT
Full Name : First-in First-out
Category : SYSTEM
Icon :

[Parameter]

I/O

Definition

Parameter Name

I/O

Designation

Setting

In-Cmd

B-VAL

Data input command (IN-CMD)

Out-Cmd

B-VAL

Data output command (OUT-CMD)

Reset B-VAL

Reset

command

FIFO-Tbl

Address input

Head address of FIFO table
(MW or DW address)

In-Data

Address input

Head address of input data
(MW or DW address)

Input

Out-Data

Address input

Head address of output data
(MW or DW address)

FIFO Table
Configuration
0 : data size
1 : input size
2 : output size
3 : number of
data stored
4 : data

Tbl-Full

B-VAL

FIFO table is full.

Tbl-Emp

B-VAL

FIFO table is empty.

Output

Tbl-Err

B-VAL

FIFO table error.