9.6 Inverter Trace Read Function (ITRC-RD)

9-13

9.6 Inverter Trace Read Function (ITRC-RD)

[Outline]

Reads out the trace data of the inverter and stores this data in the user registers. The data in the trace
buffer can be read out upon designating the number of records needed. The readout can be performed
upon designating just the necessary items in the record.
[Applicable inverters] : MP930, SVB-01, connected via 215IF

[Format]

Symbol : ITRC-RD
Full Name : Inverter-Trace Read
Category : SYSTEM
Icon :

[Parameter]

I/O

Definition

Parameter Name

I/O

Designation

Setting

Execute

B-VAL

Inverter trace read command

Abort

B-VAL

Inverter trace read forced interruption command

Type of transmission device

Dev-Typ I-REG

215IF = 1

MP930 = 4

SVB-01 = 11

Line No.

Cir-No I-REG

215IF = 1

MP930 = 1

SVB-01 = 1 to 16

Slave station No.

St-No I-REG

215IF = 1 to 64

MP930 = 1 to 14

SVB-01 = 1 to 14

Transmission buffer channel No. (No designation)

Ch-No I-REG

215IF = 1 to 3

MP930 = 1

SVB-01 = 1 to 8

Rec-Size

I-REG

Number of records to be read (1 to 64)

Select

I-REG

Items to be read (0001H to FFFFH)
Bits 0 to F correspond to trace data items 1 to 26

Input

Dat-Adr

Address input

Head address of data buffer register (address of MW or DW)

Busy

B-VAL

The reading of inverter trace data is in progress.

Complete

B-VAL

Completion of inverter trace read

Error

B-VAL

Occurrence of error

Status

I-REG

Inverter trace read execution status

Rec-Size

I-REG

Number of read records

Output

Rec-Len

I-REG

Length of read record (for 1 record)