9.7 Send Message Function (MSG-SND)

9-15

9.7 Send Message Function (MSG-SND)

[Outline]

Sends a message to the called station which is on the line and which is designated by the transmission
device type. Supports a plurality of protocol types.
The execution command (Execute) must be held until Complete or Error becomes ON.

[Transmission Devices ] CPU Module, 215IF, 217IF, 218IF, SV-01

[Protocols] MEMOBUS, non-procedural

[Format]

Symbol : MSG-SND
Full Name : Message Send
Category : SYSTEM
Icon :

[Parameter]

I/O

Definition

Parameter Name

I/O

Designation

Setting

Execute

B-VAL

Send message command

Abort

B-VAL

Send message forced interruption command

Type of transmission device

Dev-Typ I-REG

CPU module = 8
218IF = 6

215IF = 1
SVB-01 = 11

217IF = 5

Pro-Typ I-REG

Transmission

protocol

MEMOBUS = 1
non-procedural = 2

Line No.

Cir-No I-REG

CPU module = 1, 2
218IF = 1 to 8

215IF = 1 to 8
SVB-01 = 1 to 16

217IF = 1 to 24

Transmission buffer channel No.

Ch-No I-REG

CPU module=1, 2
218IF = 1 to 10

215IF = 1 to 13
SVB-01 = 1 to 8

217IF = 1

Input

Param

Address input

Head address of set data (MW, DW, #W)

Busy

B-VAL

Message is being sent.

Complete

B-VAL

The sending of the message has been completed.

Output

Error

B-VAL

Occurrence of error