Model PD650 Large Display Process Meter

Instruction Manual

11

PEAK HOLD
MAX (DISPLAY PEAK)

Captures the maximum or peak process/rate and displays it via

the front panel ENTER button

(

Dspy p

)

PEAK HOLD OR
MAX INDICATION

Front panel flashing “R” LED

LOCKOUT

Jumper JP1 labeled “LOCK” restricts modification of
programmed settings.

NON-VOLATILE
MEMORY

All programming values are stored in non-volatile memory for a
minimum of ten years if power is lost.

POWER OPTIONS

AC power: 115 or 230 VAC (field select) ±10%, 50/60 Hz, 12 VA

DC power: 22-28 VDC; 12 watts maximum

NORMAL MODE
REJECTION

64 dB at 50/60 Hz

ENCLOSURE

Die-cast aluminum, NEMA 4X, modified specifically for PDC;
four holes for ½" conduit provided at base, 3 plugs provided.

ENVIRONMENTAL

Operating temperature range: -20 to 65°C

Storage temperature range: -40 to 85°C

Relative humidity: 0 to 90% non-condensing

CONNECTIONS

Removable screw terminal blocks, accept 22 to 12 AWG wire

MOUNTING

Enclosure contains four ¼" holes for wall mounting. Panel
mounting kit available

OVERALL
DIMENSIONS

4.9" x 14.3" x 3.2" (125 mm x 362 mm x 81 mm)

WEIGHT

7.0 lbs (3.2 kg)

WARRANTY

2 years parts & labor

EXTENDED
WARRANTY

1 or 2 years, refer to the Price List for details.

Rate/Totalizer/Batch Controller Features

RATE DISPLAY
INDICATION

LED labeled “R” in lower right illuminates when meter is
displaying rate or process input.

LOW-FLOW
CUTOFF

Any input below the low-flow cutoff value will result in a display
of zero. May be set from 1 count to 100% FS, user selectable.
To disable low-flow cutoff, program cutoff value to zero.
Totalizer is based on rate display. So, inputs below the low-
flow cutoff value will not affect the totalizer.

ALTERNATING
DISPLAY

Display may be programmed to alternate between rate and
total every 10 seconds.

TOTAL DISPLAY

0 to 999,999, automatic lead zero blanking

TOTAL DECIMAL
POINT

May be set in any of the following positions: 9.99999, 99.9999,
999.999, 9999.99, 99999.9. Total decimal point is independent
of process/rate decimal point.