Model PD650 Large Display Process Meter

Instruction Manual

14

Isolated 4-20 mA Transmitter Output

CALIBRATION
RANGE

The transmitter output can be calibrated so that a 4 mA output
is produced for any process/rate measured by the meter. The
20 mA output may correspond to any process/rate that is at
least 501 counts greater or smaller than the process/rate
corresponding to 4 mA. (Ex. 4 mA = 0, 20 mA = 501) If the
span between 4 and 20 mA is less than 501 counts, an

error

message will appear.

EQUIPMENT
NEEDED

The 4-20 mA output from the meter is calibrated without the
use of a calibrator.

OUTPUT LOOP-
POWER

24 VDC ± 5% @ 20 mA, regulated. Maximum loop resistance
is 1200

Ω. Isolated from input loop-power.

ACCURACY

± 0.1% FS ± 0.004 mA

ISOLATION

500 V input-to-output or input/output-to-24 VDC supply

EXTERNAL
LOOP-POWER
SUPPLY

35 VDC maximum

OUTPUT LOOP
RESISTANCE

Power supply

Minimum loop
resistance

Maximum loop
resistance

24 VDC

10

Ω 600

Ω

35 VDC (external)

600

Ω 1000

Ω