Model PD650 Large Display Process Meter

Instruction Manual

39

Apply the signal for the first calibration point
Input 1 (INPT 1) flashes indicating that the meter
is ready to accept a signal for the first calibration
point. Apply the desired signal, typically 4 mA, and
press ENTER.

Inpt 1

Set the display for the first calibration point

The entire display will flash for three seconds. For
instructions see Five Basic Digit/Display Setting
Instructions,
page 30.

-0.000

then

01.000

then

02.000

final

03.000


If an error message is displayed during calibration, refer to Minimum Input Span
(Error Message)
, page 35.

Apply signal for the second calibration point

Input 2 (INPT 2) flashes indicating that the meter
is ready to accept a signal for the second
calibration point. Apply the desired signal, typically
20 mA, and press ENTER.

Inpt 2

Set the display for the second calibration point

Program the display as described above when the display
for the first calibration point was programmed.

-0.000

final display

12.000

Set the display for the remaining calibration points

If other calibration points were selected, they will be
displayed and can be set according to the procedure for the
first two points.
When the display for the last calibration point is accepted by
pressing ENTER, the meter will display total or process/rate.

Inpt 3