Model PD650 Large Display Process Meter

Instruction Manual

74

Relay key legend for following tables

Key

Relay condition

On Tripped

Off Reset

Ack Acknowledged

The On and Off keys do not refer to the status of the relay’s coil, which depends
on the fail-safe mode selected.
Non-Latching Relay

Automatic reset only JP5(1-4 off)

Condition

LED

Relay

Normal Off

Off

Alarm On

On

Ack (No effect)

On

On

Normal Off

Off

In this application, the meter is set up for automatic reset and non-latching relay.
Acknowledging the alarm while it is still present has no effect on either the LED
or the relay. When the alarm finally goes away, the relay automatically resets and
the LED also goes Off.

Non-Latching Relay

Automatic + manual reset at any time JP5(1-4 on)

Condition

LED

Relay

Normal Off

Off

Alarm On

On

Normal Off

Off

In this application, the meter is set up for automatic + manual reset at any time
and non-latching relay. The LED and the relay automatically reset when the
meter returned to the normal condition.

Automatic + manual reset at any time JP5(1-4 on)

Condition

LED

Relay

Normal Off

Off

Alarm On

On

Ack

On

Off

Normal Off

Off

In this application, the meter is also set up for automatic + manual reset at any
time. But this time, an operator acknowledges the alarm manually while it still
exists. This causes the relay to reset, but the LED stays On until the meter
returns to the normal condition. (Remember, for non-latching relays, the LED is
always Off during normal condition and always On during alarm condition,
regardless of the state of the relay).