Low-Flow Cutoff Programming (Cutoff)

The low-flow cutoff feature allows the meter to be programmed so that the often
unsteady output from a differential pressure transmitter at low-flow rates always
displays zero on the meter.

The totalizer in the meter accumulates based on the rate display. This means
that when the rate display is zero, even as a result of the low-flow cutoff, the
totalizer will not accumulate.

To set the low-flow cutoff point

Press ENTER, then press it again when low-flow
cutoff (Cutoff) appears.

Cutoff

The entire display will flash for three seconds. For
instructions see Five Basic Digit/Display Setting
Instructions,
page 30.
NOTE: To disable the low-flow cutoff, reprogram the value
to zero.

-19.999

then

01.000

then

01.500

final

01.520