Diagnostics and Troubleshooting

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 100 of 160

ProSoft Technology, Inc.

March 25, 2011

5.4.1 Examples

The following table shows some of the possible status indicators:

Processor
Status

MVI46-
PDPMV1
Module
Status

PROFIBUS Master
Status

PROFIBUS Master
Status LED Description

Normal
operation

RUN (ON)

ACTIVE (ON)

COM STAT
(GREEN/Solid or Flash):

Master is communicating

with slaves (GREEN) or at

least one (Blinking).
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
MVI is holding the

PROFIBUS token.
MSTR STAT (GREEN):
Master is in operate

mode.

MVI46-
PDPMV1

module does

not see the

processor

RUN (ON) or
STOP

ACTIVE (OFF)

COM STAT (OFF):
Master is not

communicating with
slaves.
DBASE STAT (GREEN):
PROFIBUS has been

configured.
TKN HOLD (OFF):
Master does not have the

token and is inactive
MSTR STAT (OFF):
Master is inactive

MVI
PROFIBUS

Master is
stopped

RUN or
STOP

ACTIVE

COM STAT (OFF):
Master is not
communicating with

configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been

configured.
TKN HOLD (GREEN):
MVI is holding the
PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.