ProSoft Technology MVI46-PDPMV1 User Manual

Page 112

Advertising
background image

Reference

MVI46-PDPMV1 ♦ SLC Platform

User Manual

PROFIBUS DPV1 Master

Page 112 of 160

ProSoft Technology, Inc.

March 25, 2011

6.1

Product Specifications

The PROFIBUS DPV1 Master module is a powerful communication interface for

Rockwell Automation

®

SLC

®

processors. Developed under license from Rockwell

Automation, the module incorporates proprietary backplane technology that

enables powerful data exchange with SLC processors.
The module supports complete Master specifications according to IEC 61158.

Acyclic parameter data can be transferred with Class 1 or Class 2 DPV1

services, allowing processors to easily communicate with slave devices

supporting PROFIBUS DPV0/V1 protocol.
The module acts as an input/output module between the PROFIBUS network

and the SLC processor. Data transfer from the processor is asynchronous with

the I/O data transfer on the PROFIBUS network.

6.1.1 General Specifications

 Single slot - 1746 backplane compatible (local or extended I/O rack only -

remote rack not supported)

 The module is recognized as an Input/Output module and has access to

processor memory for data transfer between processor and module using

M0/M1 files

 Ladder Logic is used for data transfer between module and processor.

Sample ladder file included

6.1.2 Hardware Specifications

Specification

Description

Form Factor

Single-slot SLC chassis compatible

Backplane current load

800 mA @ 5 V

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Shock

30 g operational; 50 g non-operational

Relative Humidity

5% to 95% (with no condensation)

Processor

Compatible with Rockwell Automation SLC 5/02

M0/M1 capable processors or newer

LED indicators

Module status, Backplane transfer status,
Application status, Serial activity and error LED

status