ProSoft Technology MVI46-PDPMV1 User Manual

Page 117

Advertising
background image

MVI46-PDPMV1 ♦ SLC Platform

Reference

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 117 of 160

March 25, 2011

Module Configuration Data (M1 Word Offsets 0 to 12)

M1 Word Offset

Description

0 to 4

Unique module 10-byte pattern as text "MVI4PDPMV1"

5

Reserved for future use

6

User-configured PROFIBUS input data size stated as a word count.

7

User-configured PROFIBUS output data size stated as a word count.

8

Reserved for future use

9

Reserved for future use

10

Reserved for future use

11

Low byte: User-configured flag to indicate if input data is byte-swapped in
each word before placing in the input image for the controller. If 0, no

swapping. If not 0, then swap bytes in each word

High byte: User-configured flag to indicate if output data is byte-swapped in
each word after receiving from the output image of the controller. If 0, no

swapping. If not 0, then swap bytes in each word

12

Low byte: Module software major version number

High byte: Module software minor version number

Status Data in the Input Image

PROFIBUS Slave Status Data (M1 Word Offsets 13 to 36)

M1 Word Offset

Description

13 to 20

Fieldbus data - slave configuration list
(8 words: 16 slave addresses per word)
0=No configured slave at slave address
1=Configured slave at slave address

21 to 28

Fieldbus data - slave data transfer list
(8 words: 16 slave addresses per word)
0=Slave not communicating with Master
1=Slave communicating with Master

29 to 36

Fieldbus data - slave diagnostic list
(8 words: 16 slave addresses per word)
0=No diagnostic data for slave
1=Diagnostic data is being generated for slave